2023-07-10 07:47:10 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23060579 |
| 7/7/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET C-1: DRINKING FOUNTAINS ARE REQUIRED FIXTURES |
| FOR FACTORY/INDUSTRIAL, BUSINESS, AND ASSEMBLY |
| OCCUPANCIES- TABLE 403.1 FBC P. A MINIMUM OF TWO SHALL |
| BE INSTALLED- ONE HI AND ONE LO- SEC. 410.3. PLEASE |
| REVISE THE DRAWINGS TO SHOW THE LOCATION, ACCESSIBILITY |
| DETAILS, AND PLUMBING PIPING REQUIREMENTS. |
| |
| 2) 7P: PROVIDE A VENT FOR THE MOP SINK FIXTURE TRAP- |
| SECS. 909.1, 910.1 FBC P. |
| |
| 3) 7P: WPB BUILDING DEPT. PERMITTING RECORDS DO NOT |
| SHOW ANY PERMITS ON FILE FOR THE EXISTING BATHROOMS, |
| AND 3-COMPARTMENT SINK. PLEASE PROVIDE COMPLETE |
| PLUMBING PLANS INCLUDING THE FOLLOWING ITEMS AS |
| REQUIRED BY SECS. 107.2.1 & 107.3.5.1.3 WPB. |
| |
| A) WATER PIPING LAYOUT PLAN: SHOW WATER SERVICE |
| ENTRANCE, LOCATION OF METER AND BACKFLOW PREVENTER, AND |
| HOT AND COLD WATER DISTRIBUTION PIPING RUNS THROUGH THE |
| TENANT SPACE. |
| |
| B) SANITARY PIPING LAYOUT PLAN: SHOW UNDERSLAB SANITARY |
| AND GREASE WASTE PIPING RUNS THROUGH THE TENANT SPACE. |
| |
| C) PLUMBING RISER DRAWINGS INCLUDING SANITARY, GREASE |
| WASTE, AND WATER DISTRIBUTION. |
| |
| D) PLUMBING FIXTURE AND APPLIANCE SCHEDULE. |
| |
| E) WATER HEATER AND TANK EQUIPMENT SCHEDULES AND PIPING |
| DIAGRAM. PLEASE INCLUDE THE PAN DRAIN PIPING |
| TERMINATION LOCATION IN THE DIAGRAM. |
| |
| E) GREASE WASTE INTERCEPTOR: A GREASE INTERCEPTOR IS |
| REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES WITH |
| GREASE LADEN WASTE. PLEASE SHOW THE LOCATION OF THE |
| INTERCEPTOR AND PROVIDE AN EQUIPMENT SCHEDULE, SIZING |
| CALCULATIONS, PIPING DIAGRAM. PLEASE NOTE A SEPARATE |
| PERMIT IS REQUIRED FOR INSTALLATION- SEE NOTE BELOW. |
| |
| F) PLUMBING DEVICES: THE WATER PIPING PLANS SHALL SHOW |
| THE LOCATIONS OF REQUIRED MIXING VALVES, INLINE |
| BACKFLOW PREVENTERS TO APPLIANCES AND EQUIPMENT, AND |
| WATER HAMMER ARRESTORS. PLEASE NOTE THE FOLLOWING CODE |
| SECTIONS. |
| |
| SEC. 419.5 REQUIRES TEMPERED WATER DELIVERY FROM THE |
| PUBLIC LAVATORY IF THE LAVATORY HAS HOT WATER SUPPLY. |
| |
| SEC. 607.1.1 REQUIRES A MEANS OF LIMITING THE HOT WATER |
| TEMPERATURE DELIVERY AT THE FIXTURES OTHER THAN THE |
| THERMOSTAT ON THE WATER HEATER. |
| |
| SEC. C404.5.1 FBC ENERGY LIMITS THE LENGTH OF A |
| 1/2-INCH HOT WATER SUPPLY PIPE TO A PUBLIC LAVATORY TO |
| 2 FT. |
| |
| 4) CIVIL PLANS ARE REQUIRED FOR WORK INVOLVING NEW OR |
| ALTERED UNDERGROUND SERVICE PIPING INCLUDING WATER, |
| SANITARY, STORM DRAINAGE, FIRE LINES, GAS AND ELECTRIC. |
| THE PLANS SHALL SHOW POINTS OF CONNECTIONS TO EXISTING |
| MAIN SERVICE PIPES. |
| |
| 5) DUE TO A CHANGE IN PROCESS, GREASE INTERCEPTOR |
| PERMIT APPLICATION IS REQUIRED TO BE SUBMITTED PRIOR TO |
| PLUMBING PLAN REVIEW APPROVAL. YOU CAN SUBMIT AN |
| APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A |
| CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| APPLICATION TO [email protected] . YOU WILL |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |