Plan Review Notes
Plan Review Notes For Permit 23060579
Permit Number 23060579
Review Stop G
Sequence Number 1
Notes
Date Text
2023-07-10 11:02:451ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23060579
 7/10/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 5A GAS RISER CORRECTIONS:
  
 A) THE GAS LOAD CALCULATIONS SHOW TWO 90,000 BTU
 ROASTERS AT TOTAL LOAD OF 180,000 BTUH. THE RISER SHOWS
 ONE ROASTER AT 144,000 BTUH.
  
 B) THE 3/4-INCH MAIN SUPPLY PIPE IS UNDERSIZED FOR A
 TOTAL LOAD OF 180,000 BTUH AT 37 FT. TOTAL DEVELOPED
 LENGTH- TABLE 402.4(2) FBC FG.
  
 2) 5A: THE METER IS CALLED OUT AS EXISTING. PLEASE
 MODIFY THE RISER DRAWING TO SHOW ALL EXISTING PIPING
 AND APPLIANCES THAT ARE CONNECTED TO THE SYSTEM- SECS.
 401.3 & 401.4 FBC P.
  
 3) 5A: COMBUSTION AIR CORRECTIONS:
  
 A) REMOVE MECHANICAL SUPPLY CALCULATION. IT IS NOT
 CONSISTENT WITH THE TWO OUTDOOR AIR OPENINGS METHOD
 SHOWN ON THE PLANS.
  
 B) REFER TO SEC. 304.6.1 AND REVISE THE CALCULATION FOR
 EACH OPENING TO INDICATE 1 SQ. INCH OF FREE AIR PER
 4000 BTUH REQUIRED, OR 45 SQ. INCHES PER OPENING,
  
 C) SHOW THE UPPER OPENING WILL COMMENCE WITHIN 12
 INCHES OF THE TOP OF THE ENCLOSURE- SEC. 304.6.1.
  
 4) COFFEE ROASTER VENTING: A COMPLETE REVIEW OF THE
 VENTING SYSTEM CANNOT BE ACCOMPLISHED WITHOUT SUBMITTAL
 OF MANUFACTURER'S SPECIFICATIONS FOR THE ROASTERS AND
 FOR THE VENT DUCTS- SECS. 305.1, 503.4 & 503.7 FBC FG.
 BASED ON THE NOTES ON THE PLAN THE DUCTS SHALL BE UL
 LISTED AND LABELED AND SUITABLE FOR 1000 DEGREES F
 CONTINUOUS, AND 1400 DEGREES F INTERMITTENT. REFER TO
 SEC. 202 AND ADD NOTES ON THE PLAN TO INDICATE THE
 CATEGORY OF THE COFFEE ROASTERS- 1, II, II, OR IV, AND
 THE TYPE OF VENTING SYSTEMS- FORCED DRAFT, INDUCED
 DRAFT, MECHANICAL DRAFT OR NATURAL DRAFT. PLEASE NOTE
 ALL SUBMITTALS SHALL BEAR THE APPROVAL STAMP OF THE
 ENGINEER OF RECORD- SEC. 107.3.4 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  