2023-07-18 11:22:59WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23060579
 ADD: 2603 PINEWOOD
 CONT: BUILTMORE CONTRACTING INC.
 TEL: 561-331-1476
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 18TH/23
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN:
 1A) BOTH THE LIFE SAFETY PLAN AND FLOOR PLAN SHOW AN
 ENLARGED UNISEX RESTROOM, BUT THE EXISTING WALL LINES
 OF THE OLD RESTROOM STILL SHOW WITH AN INSWING DOOR.
 THE PLUMBING FLOOR PLAN SHOWS THE WALL CONFIGURATION
 CORRECTLY. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
 1B) STORAGE ROOM 909 SQ. FT. SHOWS AN EMERGENCY BATTERY
 LIGHT WALL PACK WITH EXIT SIGN BUT THERE IS NO EXIT
 BENEATH THE BATTERY BACKPACK. DISCREPANCY IN PLANS.
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 1C) NEITHER OF THE LARGE STORAGE AREAS SHOW THE EXIT
 DIRECTIONAL NOR THE 2 SMALL STORAGE ROOMS SHOW EXIT
 LIGHTS FROM THE ROOMS. 2020 FBC-BUILDING CODE SECTION
 1013.1.
 1D) THE TASTING ROOM SHOWS 6 CHAIRS WITH TABLE LOT THEN
 A 4 FOOT SECTION OF TABLE TOP, THE PLANS ARE NOT CLEAR
 AS TO THE HEIGHT OF EITHER SECTION OF THE TABLE, IF THE
 ONE WITHOUT A CHAIR IS TO REPRESENT AN ACCESSIBLE
 SECTION OF THE TABLE, PLANS ARE NOT CLEAR. THE LIFE
 SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
 1E) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1F) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 2) THE LIFE SAFETY PLAN NOR FLOOR PLAN SHOW WALL
 ELEVATIONS OF THE NEW ACCESSIBLE RESTROOM AND ACCESSIB
 2A) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE
 WATER CLOSET. SECTION 604.3
 2B) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE
 LAVATORIES. SECTION 606.2.
 2C) TURNING SPACE DIAMETERS. SECTION 304.3
 2D) CENTERLINE OF THE WATER CLOSETS FROM THE NEAREST
 SIDE WALL. SECTION 604.2.
 2E) HEIGHT OF THE WATERCLOSET SEATS FROM FINISH FLOOR.
 SECTION 604.4.
 2F) HEIGHT OF THE LAVATORIES AND OR SINKS OR COUNTER
 SURFACES FROM THE FINISH FLOOR. SECTION 606.3.
 KNEE & TOE SPACE REQUIRED BY SECTION 306.2 TOE
 CLEARANCE, 306.3 KNEE CLEARANCES, 2020 FBC-
 ACCESSIBILITY CODE. INSULATE PIPES PER SECTION
 2G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE BOTTOM EDGE OF THE REFLECTIVE SURFACE, MIRRORS
 ABOVE SINKS. SECTION 606.3.
 2H) LOCATIONS, LENGTHS AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS SEE SECTION 604.5, 609.4 &.
 FIGURE 604.
 2I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS.
 SECTION 604.6.
 2J) CENTERLINES OF THE TOILET DISPENSER MEASURED FROM
 THE FRONTS OF THE WATER CLOSET. SECTION & FIGURE 604.7
 2K) 2020 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH 602.7.
 2L) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL
 NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
 2M) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED.
 2N) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
  
  
  
  
 3) NEITHER THE LIFE SAFETY PLAN NOR THE FLOOR PLANS
 PROVIDE WALL FINISH SCHEDULE FOR RESTROOMS AND SERVICE
 SINKS. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2020 FBC-BUILDING 1210.2.2 WALLS & PARTITIONS WITHIN 2
 FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT
 OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 4) THE SITE PLAN SHOWS AN EXTENDED STRIPPED WALKWAY TO
 BUILDING. THE SITE PLAN APPEARS TO BE POSSIBLY HAVE A
 CANOPY NOT SHOWN ON THE LIFE SAFETY PLAN NOR ANY FLOOR
 PLAN. WHICH DOORWAY IS GOING TO BE THE MAIN ENTRY/ EXIT
 DOORWAY NEEDING TO SHOW COMPLIANCE WITH 2020
 FBC-ACCESS. CODE CHANGES IN LEVEL 303.2 AND 303.3.
 WHERE CHANGES IN LEVEL ARE PERMITTED IN THE FLOOR OR
 GROUND SURFACES, THEY SHALL COMPLY WITH SECTION 303.
 SEE 303.1 & 303.2.
  
 5) THIS PERMIT IS FOR AN INTERIOR REMODEL, NOT EXISTING
 PARKING, OR ACCESSIBLE PARKING NOR EXTEND STRIPPING TO
 BUILDING. CLARIFICATION ONLY, NO ACTION IS REQUIRED ON
 THE DESIGNER???S PART.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER