2023-06-24 08:36:40 | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC R 303.5.1, INTAKE OPENINGS ARE TO BE A NOT LESS | | THAN 10'. SUBMIT A SURVEY SHOWING LOCATION OF PROPOSED | | GENERATOR, INCLUDE DISTANCE TO OPENINGS. | | | | 2. THE GENERATOR PAD IS DESIGNED FOR FBC 2010. | | GOVERNING CODE IS FBC 2020. REVISE. | | | | 3. THE GENERATOR PAD ENGINEERING IS NOT DIGITALLY OR | | ELECTRONICALLY SIGNED, FS471. UPLOAD DIGITALLY OR | | ELECTRONICALLY SIGNED ENGINEERING - SIGNATURE TO BE IN | | ACCORDANCE WITH FBPE RULES. | | | | 4. THE GENERATOR PAD ENGINEERING IS FOR GENERATORS FROM | | 8KW TO 22KW, A 24KW GENERATOR IS PROPOSED. DIMENSIONS | | OF GENERATOR PROPOSED ARE NOT CONSISTENT WITH THE | | DIMENSIONS/WEIGHT ON ENGINEERING. | | | | | | | | |
|