 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 303.5.1, INTAKE OPENINGS ARE TO BE A NOT LESS
 THAN 10'. SUBMIT A SURVEY SHOWING LOCATION OF PROPOSED
 GENERATOR, INCLUDE DISTANCE TO OPENINGS.
  
 2. THE GENERATOR PAD IS DESIGNED FOR FBC 2010.
 GOVERNING CODE IS FBC 2020. REVISE.
  
 3. THE GENERATOR PAD ENGINEERING IS NOT DIGITALLY OR
 ELECTRONICALLY SIGNED, FS471. UPLOAD DIGITALLY OR
 ELECTRONICALLY SIGNED ENGINEERING - SIGNATURE TO BE IN
 ACCORDANCE WITH FBPE RULES.
  
 4. THE GENERATOR PAD ENGINEERING IS FOR GENERATORS FROM
 8KW TO 22KW, A 24KW GENERATOR IS PROPOSED. DIMENSIONS
 OF GENERATOR PROPOSED ARE NOT CONSISTENT WITH THE
 DIMENSIONS/WEIGHT ON ENGINEERING.
  
  
  
  