Plan Review Notes
Plan Review Notes For Permit 23060501
Permit Number 23060501
Review Stop P
Sequence Number 1
Notes
Date Text
2023-07-14 17:41:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23060501
 7/14/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. GENERAL/ADMINISTRATIVE COMMENTS.
  
 1) THE ENERGYGAUGE REPORT DOES NOT PROVIDE COMPLIANCE
 DATA FOR THE WATER HEATING AND PIPING SYSTEMS- SEC.
 C404.1 FBC EC.
  
 2) SEPARATE PERMITS REQUIRED INCLUDE THE POTABLE WATER
 BACKFLOW PREVENTER, GROUND FLOOR SOLIDS INTERCEPTORS
 AND OIL SEPARATOR, AND 6TH FLOOR GREASE INTERCEPTOR-
 SEC. 105.1 & 107.2.1 WPB. PLEASE NOTE THE SUBMITTED
 PLUMBING PLANS FOR THE BUILDING WILL NOT BE APPROVED
 UNTIL PERMIT APPLICATIONS FOR THE ITEMS LISTED ABOVE
 HAVE BEEN SUBMITTED. YOU CAN SUBMIT APPLICATIONS TBD
 (TO BE DETERMINED) IF YOU DO NOT HAVE CONTRACTORS
 SELECTED BY EMAILING COMPLETED PERMIT APPLICATIONS TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE ALL
 OF THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE PUBLIC AND
 PRIVATE POOLS AND SPAS HOWEVER THE PLUMBING FLOOR PLANS
 AND RISERS SHOW POOL WASTEWATER DRAINING INTO THE
 SANITARY SYSTEM WHICH IS PROHIBITED PER SEC. 90-126
 (B)(5) WPB CODE OF ORDINANCES. PLEASE NOTE THE
 FOLLOWING INFORMATION.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 - THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 4) SEPARATE PERMITS ARE REQUIRED FOR THE IRRIGATION
 SYSTEM AND SYSTEM BACKFLOW PREVENTER. CURRENTLY NO
 PLANS HAVE BEEN SUBMITTED FOR REVIEW. PLANS SHALL BE
 SUBMITTED UNDER THE SEPARATE PERMITS- SEC. 107.2.1 WPB.
  
 2. ARCHITECTURAL COMMENTS.
  
 5) 4) SHEETS ALS.0.0, ALS.0.2 & ALS.0.3: PLEASE REFER
 TO SEC. 233 FBC ACCESSIBILITY. BASED ON SECS 233.3.1 &
 233.3.1.1 AT LEAST 5% OF THE TOTAL NUMBER OF
 RESIDENTIAL DWELLING UNITS SHALL BE PROVIDED WITH
 MOBILITY FEATURES COMPLYING WITH SECS. 809.2- 809.4 AND
 SHALL BE ON AN ACCESSIBLE ROUTE; AND AT LEAST 2% SHALL
 BE PROVIDED WITH COMMUNICATION FEATURES COMPLYING WITH
 809.4. THESE REQUIREMENTS ARE SEPARATE FROM COMPLIANCE
 WITH THE FAIR HOUSING DESIGN ACT REQUIREMENTS. REFER TO
 SEC. 233.3.5 DISPERSION AND PROVIDE A LIST OR SCHEDULE
 ON THE PLAN SHOWING THE LOCATIONS OF THE UNITS, AND
 REVISE THE ARCHITECTURAL AND PLUMBING PLANS WHERE
 REQUIRED.
  
 A) ALS.02 & ALS.0.3: THE PLANS INDICATE THE R2 CONDO
 UNITS ARE DESIGNED IN ACCORDANCE WITH THE FAIR HOUSING
 DESIGN ACT MANUAL (1998). TO HELP EXPEDITE THE REVIEW
 AND INSPECTION OF THE CONDO BATHROOMS PLEASE REFER TO
 PAGES 7.34 & 7.35 OF THE FHDA AND INDICATE WHICH DESIGN
 SPECIFICATION HAS BEEN CHOSEN- SPECIFICATION A OR B.
 PLEASE PROVIDE THE SPECIFICATION TYPE ON ALS.02,
 ALS.04, AND ON THE ENLARGED A, B, C & D UNIT PLANS-
 SHEETS A-9.10.1, A-9.11.1, A-9.12.1 & A-9.13.1.
  
 B) ALS.0.0, ALS.0.2 & ALS.0.3: AS NOTED THERE ARE
 DESIGN DIFFERENCES BETWEEN AN FBC ACCESSIBLE (ADA
 COMPLIANT) DWELLING UNITS AND A FHDA COMPLIANT UNITS.
 PLEASE REFER TO SEC. 809.4 FBC ACCESSIBILITY AND
 PROVIDE SEPARATE ENLARGED ACCESSIBLE UNIT DRAWINGS WITH
 THE FOLLOWING COMPLIANCE DETAILS PER SEC. 603- 610 FBC
 ACCESSIBILITY. PLEASE NOTE MANY OF THESE SECTIONS HAVE
 EXCEPTIONS WHICH ALLOW FOR JUST GRAB BAR BACKING TO BE
 INSTALLED INSTEAD OF COMPLETE GRAB BARS.
  
 1. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
  
 2. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
  
 3. TURNING SPACE DIAMETERS- SEC. 304.3.
  
 4. CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
  
 5. HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
  
 6. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SEC. 606.3.
  
 7. HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3.
  
 8. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2.
  
 9. CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
  
 10. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 11. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 BATHTUBS- SEC. 607.2.
  
 12. BATHTUB PERMANENT OR REMOVAL SEAT DETAILS- SEC.
 607.3.
  
 13. BATHTUB GRAB BAR DETAILS- SEC. 607.4.
  
 14. BATHTUB CONTROLS DETAILS- SECS. 607.5- 607.6.
  
 15. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SHOWER- SECS. 608.2.1 & 608.2.2.
  
 16. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 AND
 608.3.2.
  
 17. LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS
 IN THE SHOWERS- SECS. 608.5.1 & 608.5.2.
  
 18. LOCATIONS OF ACCESSIBLE SHOWER SEATS AND MOUNTING
 DETAILS-
  
 6) ALS.02, ALS.0.3: PROVIDE GRAB BAR BACKING DETAILS
 FOR THE CONDO SHOWERS IN COMPLIANCE WITH PAGES 6.12 &
 6.13 FDHA MANUAL.
  
 7) SHEETS A-9.10.1, A-9.11.1, A-9.12.1 & A-9.13.1,
 A-9.14.1, A-9-15.1, A-9.16.1,A-17.1, A-18.1: PLEASE
 PROVIDE FHDA COMPLIANCE DETAILS ON THE FLOOR PLANS OR
 PROVIDE NOTES REFERENCING SHEETS ALS.02 & ALS.03 FOR
 DETAIL LOCATIONS.
  
 8) ALS.1.1 PLUMBING FIXTURE COUNT TABLE: REQUIRED AND
 PROVIDED COUNTS CANNOT BE UNISEX BECAUSE SEPARATE
 FACILITIES ARE REQUIRED FOR MALE AND FEMALE USE UNLESS
 ONLY ONE WATER CLOSET FOR EACH IS REQUIRED- SECS. 403.2
 & 403.2.1 FBC P. PLEASE LABEL THE BATHROOMS ON ALL 1ST
 FLOOR PLANS AS EITHER MALE OR FEMALE.
  
 9) P1.6.2A: SHOW THE WEST POOL OUTDOOR SHOWER LOCATION-
 SEC. 454.1.6.2 FBC B.
  
 10) A9.1.1A: PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAMS
 AND DIMENSIONS AT THE ACCESSIBLE EMPLOYEE LOUNGE SINK
 AND WHEEL CHAIR ACCESSIBLE DRINKING FOUNTAIN- SECS.
 602.2 & 606.2 FBC ACC. A) PLEASE PROVIDE AN ELEVATION
 DETAIL FOR THE DRINKING FOUNTAINS SHOWING THE KNEE AND
 TOE CLEARANCES AND SPOUT HEIGHTS- SECS 602.2- 602.7 FBC
 ACC.
  
 11) A9.1.6: SHOW THE HEIGHTS OF THE WATER CLOSET SEATS
 MEASURED FROM THE FINISHED FLOORS- SEC. 604.4 FBC ACC.
  
 12) A9.1.6: SHOW THE KNEE AND TOE CLEARANCES FOR THE
 LAVATORIES- SECS. 606.2, FIG. 306.2 & 306.3 FBC ACC.
  
 13) A9.7.5: PROVIDE AN ELEVATION DETAIL FOR THE
 DRINKING FOUNTAINS SHOWING THE KNEE AND TOE CLEARANCES
 AND SPOUT HEIGHTS- SECS 602.2- 602.7 FBC ACC.
  
 14) A9.7.6, A9.7.7, & A9.7.8: MISSING FBC ACC DETAILS:
  
 A) HEIGHTS OF THE ACCESSIBLE WATER CLOSET SEATS
 MEASURED FROM THE FINISHED FLOORS- SEC. 604.4.
  
 B) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE
 LAVATORIES- SECS. 606.2, FIG. 306.2 & 306.3.
  
 C) ACCESSIBLE URINAL RIM HEIGHT FROM THE FINISHED
 FLOOR- SEC. 605.2.
  
 15) A9.7.1B, A9.7.10: THE MEN'S AND WOMEN'S SHOWERS
 SHALL BE ACCESSIBLE AS REQUIRED BY SEC. 213.3.6 FBC
 ACC. PROVIDE THE FOLLOWING DETAILS FBC ACC.
  
 A) GRAB BAR LOCATIONS, LENGTHS AND MOUNTING HEIGHTS-
 SEC. 608.3.3. PLEASE NOTE THE SEATS WILL HAVE TO BE
 RELOCATED TO ALLOW INSTALLATION OF THE SIDE WALL GRAB
 BARS.
  
 B) THE CONTROLS, FAUCETS, AND SHOWER SPRAY SHALL BE
 RELOCATED TO THE SIDE WALL ADJACENT TO THE RELOCATED
 SEAT AT A POINT 27 INCHES MAXIMUM FROM THE SIDE WALL
 BEHIND THE SEAT OR SHALL BE LOCATED ON THE BACK WALL
 OPPOSITE THE SEAT 15 INCHES MAXIMUM, LEFT OR RIGHT, OF
 THE CENTERLINE OF THE SEAT.
  
 C) SHOW THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN
 48 INCHES ABOVE THE SHOWER FLOOR.
  
 3. PLUMBING COMMENTS
  
 16) P1.0.0, P1.1.1A, P1.1.1B, P1.1.1C- FLOOD HAZARD:
 FLOOD MAPS INDICATE PORTIONS OF THE BUILDING MAY BE
 CONSTRUCTED IN AN AE FLOOD HAZARD ZONE. PLEASE NOTE THE
 FOLLOWING.
  
 A) REFER TO SEC. 309.2 FBC P FLOOD HAZARD AND SEC. 7.3
 ASCE 24-14: THE PLUMBING SYSTEMS, EQUIPMENT, FIXTURES
 AND OTHER COMPONENTS SYSTEM SHALL BE INSTALLED ABOVE
 THE DESIGN FLOOD ELEVATION HEIGHT, OR MEET THE
 EXCEPTION UNDER 309.2.
  
 B) UNDERGROUND PIPING AND PLUMBING SYSTEMS SHALL BE
 BURIED TO A DEPTH SUFFICIENT TO PREVENT MOVEMENT,
 SEPARATION, OR LOSS DUE TO FLOODING AND EROSION UNDER
 DESIGN FLOOD CONDITIONS- 7.3.1 ASCE 24-14.
  
 C) OPENINGS IN THE PLUMBING SYSTEMS BELOW THE DESIGN
 FLOOD ELEVATION HEIGHT SHALL BE PROTECTED WITH
 AUTOMATIC BACKWATER VALVES. SHOW COMPLIANCE WHERE
 REQUIRED WITH NOTES AND DETAILS ON THE PLANS- SEC.
 714.1 FBC P.
  
 17) P1.0.0: PROVIDE CIVIL PLANS SHOWING WATER, FIRE AND
 GAS SERVICE PIPING CONTINUATIONS AND CONNECTIONS TO
 MAINS, AND SANITARY AND STORM DRAIN CONTINUATIONS AND
 CONNECTIONS- SEC. 107.2.1 WPB.
  
 18) P1.1.1A, P1.1.1B, P1.1.1C: TO HELP EXPEDITE THE
 REVIEW PLEASE SHOW THE DFU TOTALS AT THE SANITARY
 RISERS, BRANCHES, AND MAIN BUILDING DRAINS- TABLES
 710.1(1) & 710.1(2) FBC P.
  
 A) SHOW THE GPM TOTALS AT STORM RISERS, BRANCHES, AND
 MAIN DRAINS- TABLES 1106.2, 1106.3 FBC P.
  
 B) TO HELP EXPEDITE THE REVIEW PLEASE LABEL SANITARY
 PIPING (S) AND STORM PIPING (ST)- SEC. 107.2.1 WPB.
  
 19) P1.1.1B, P1.1.1C, P4.1.1: PROVIDE EQUIPMENT
 SCHEDULES AND SIZING CALCULATIONS FOR THE SOLIDS
 INTERCEPTORS, THE OIL SEPARATOR, AND THE LINT TRAP-
 SECS. 1003.1, 1003,4,2, & 1003.6 FBC P.
  
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR EACH WITH
 ENGINEER'S APPROVAL STAMP- SEC. 107.3.4 WPB.
  
 20) P1.1.C & P4.1.1: IT APPEARS THE SOLIDS INTERCEPTOR
 IN THE TRASH ROOM IS NOT VENTED- SEC. 1003.9 FBC P.
  
 21) P1.1.2A, P4.2.1: PLEASE PROVIDE WATER DISTRIBUTION
 DESIGN CRITERIA- SEC. 604.3 FBC P.
  
 22) P4.2.1: COMPLETE WATER RISER DRAWINGS FROM THE
 GROUND FLOOR THROUGH THE FLOOR INTERVALS TO THE ROOF
 HAVE NOT BEEN PROVIDED. PLEASE PROVIDE THE RISERS- SEC.
 107.3.5.1.3 WPB. TO HELP EXPEDITE THE REVIEW PLEASE
 NUMBER THE INDIVIDUAL RISERS AND PROVIDE MATCHING
 NUMBERS AT THE RISER LOCATIONS SHOWN ON THE GROUND
 FLOOR ISOMETRIC DRAWINGS.
  
 A) THE WATER RISER DRAWINGS SHALL SHOW PIPE SIZES FROM
 FLOOR-TO-FLOOR INTERVALS, PIPE SIZES AT UNIT ENTRANCES,
 AND LOCATIONS OF SHUTOFF VALVES AND PRV'S WHERE
 REQUIRED- SECS 604.4, 604.7 & 606.1 FBC P.
  
 23) P4.1.1: COMPLETE CONVENTIONAL SANITARY
 DRAINAGE/VENT RISER DRAWINGS FROM THE GROUND FLOOR
 THROUGH THE FLOOR INTERVALS TO THE ROOF HAVE NOT BEEN
 PROVIDED. PLEASE PROVIDE THE RISERS- SEC. 107.3.5.1.3
 WPB. TO HELP EXPEDITE THE REVIEW PLEASE NUMBER THE
 INDIVIDUAL RISERS AND PROVIDE MATCHING NUMBERS AT THE
 RISER LOCATIONS SHOWN ON THE GROUND FLOOR ISOMETRIC
 DRAWINGS.
  
 B) THE CONVENTIONAL SANITARY RISERS SHALL SHOW SOIL,
 WASTE, AND VENT STACK SIZES FROM FLOOR-TO-FLOOR,
 LOCATIONS AND SIZES OF OFFSETS AND RELIEF VENTS WHERE
 REQUIRED, VENT TO ROOF LOCATIONS, CLEANOUT LOCATIONS,
 AND DFU CALCULATIONS- SECS. 710.1, 904.1, 904.2, 904.4,
 904.5, 906.1, 907.1, & 908.1 FBC P.
  
 24) P4.1.1 & P.503: CONCERNING THE TUFF-RITE SOVENT
 SYSTEM PLEASE REFER TO SEC. 316 FBC P. THE SYSTEM IS
 DEFINED AS AN ALTERNATIVE ENGINEERED DESIGN WHICH
 REQUIRES THE ENGINEER OF RECORD TO SUBMIT TECHNICAL
 DATA TO SUBSTANTIATE THE PROPOSED ALTERNATIVE DESIGN
 AND TO PROVE THE PERFORMANCE MEETS THE INTENT OF THE
 CODE- SEC. 316.1.3. PLEASE PROVIDE THE FOLLOWING ITEMS
  
 A) ENGINEER'S LETTER TO THE BUILDING OFFICIAL WITH
 SUFFICIENT EVIDENCE TO REQUEST APPROVAL OF THE
 ALTERNATIVE SYSTEM.
  
 B) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS WITH ENGINEER'S APPROVAL STAMP.
  
 C) SEPARATE SITE-SPECIFIC FLOOR PLANS AND COMPLETE
 RISER DRAWINGS. THE CURRENT PLANS SUBMITTED CAN BE
 SEPARATED, MODIFIED, LABELED PROPERLY AND PROVIDED WITH
 ADDITIONAL SITE-SPECIFIC INFORMATION SUCH AS PIPE
 SLOPES AND HORIZONTAL PIPE LENGTHS ETC.- SEC. 316.1.4.
 PLEASE NOTE WHERE REQUIRED THE RISERS SHALL BE
 CONTINUOUS FROM GROUND FLOOR TO ROOF.
  
 25) P.4.1.1: SHOW REQUIRED TRAPS FOR THE DW 1 DRAINS-
 SEC. 1002.1 FBC P.
  
 26) P1.1.2A, P1.1.2B, P4.2.1: COLD OR TEMPERED WATER
 SHALL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC
 P.
  
 27) P1.1.2A, P1.1.2B, P4.2.1: THE 1/2-INCH HOT WATER
 FIXTURE SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING
 THE MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT
 WATER SOURCES- TABLE C404.5.1 FBC ENERGY.
  
 28) P4.2.1: SHOW FULL-OPEN SHUT OFF VALVES AT BASE OF
 THE WATER RISERS- SEC. 606.1 (4) FBC P.
  
 29) P1.2.1A, P1.3.1A, P1.4A: THE DRAWINGS APPEAR TO
 SHOW AREA DRAINS (AD) ON THE WEST SIDE DRAINING INTO
 THE SANITARY WHICH IS PROHIBITED PER SEC. 90-126 (B)
 WPB CODE OF ORDINANCES.
  
 30) P1.5.2C NOTE 6: A BACKFLOW PREVENTER IS REQUIRED
 FOR THE MAKEUP WATER LINE TO THE POOL EQUIPMENT- SEC.
 608.3 FBC P.
  
 31) P1.6.1A: THE PLAN APPEARS TO SHOW A SANITARY DRAIN
 LINE PENETRATING THE INTERIOR EXIST STAIRWAY 2 WHICH IS
 PROHIBITED PER SEC. 1023.5 FBC B.
  
 32) P1.6.1B KITCHEN GREASE INTERCEPTOR: PLEASE PROVIDE
 THE FOLLOWING ITEMS PER SEC. 1003.3.5 FBC P.
  
 A) EQUIPMENT SCHEDULE- MAKE AND MODEL, GALLON SIZE.
  
 B) SIZING CALCULATIONS.
  
 C) ENLARGED PIPING DIAGRAM SHOWING DRAIN PIPE SIZES AND
 RUNS FROM FIXTURES, OUTLET AND VENT PIPING SIZES AND
 RUNS.
  
 D) PLEASE NOTE DISCHARGES FROM HAND SINKS, ICE MAKER
 AND ICE BINS SHALL NOT DRAIN INTO THE INTERCEPTOR- SEC.
 1003.3.1 FBC P.
  
 E) P4.1.2: SHOW THE INTERCEPTOR LOCATION ON THE RISER-
 SEC. 107.2.1 WPB.
  
 33) P1.6.1B, P1.6.2B: PLEASE PROVIDE A PLUMBING
 APPLIANCE AND FIXTURE EQUIPMENT SCHEDULE AND
 CORRELATING PLAN FOR THE KITCHEN- SEC. 107.2.1 WPB.
  
 34) P1.6.2A, P1.6.2B: PROVIDE BACKFLOW PREVENTERS FOR
 WATER SUPPLY LINES TO POOL EQUIPMENT AND STEAM
 GENERATORS- SEC. 608.3 FBC P.
  
 35) P1.6.2A, P1.6.2B: COLD OR TEMPERED WATER SHALL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5.
  
 36) P1.6.2A, P1.6.2B: THE 1/2-INCH HOT WATER FIXTURE
 SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING THE
 MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT WATER
 SOURCES- TABLE C404.5.1 FBC ENERGY.
  
 37) P2.0.1, A2.0.1, A8.4.1: THE OVERFLOW SCUPPERS SIZES
 ARE NOT SHOWN AND THE SCUPPER LOCATIONS ON THE PLANS
 DON'T MATCH- SEC. 1108.3 FBC P.
  
 38) P4.01 & P4.02: THE STORM RISERS DO NOT SHOW THE GPM
 FLOWS FROM THE AD'S, PD'S, AND CND'S, AND ALSO THE
 ACCUMULATIVE TOTALS BRANCH CONNECTIONS AND MAIN
 OUTFLOWS- SEC. 1106.2 FBC P.
  
 39) P3.1.2, P3.2.2, P3.4.2, P3.5.2, P3.6.1, P3.7.1,
 P3.8.2, P3.9.2, P3.10.3, P3.11.3, P3.11.4, P3.12.3,
 P3.12.4: SHOW WATER SHUTOFF LOCATIONS AT UNIT
 ENTRANCES- SEC. 606.1 (6) FBC P.
  
 40) P3.1.2, P3.2.2, P3.4.2, P3.5.2, P3.6.1, P3.7.1,
 P3.8.2, P3.9.2, P3.10.3, P3.11.3, P3.11.4, P3.12.3,
 P3.12.4: IT APPEARS THE DEVELOPED LENGTH OF THE HOT
 WATER TO SOME OF THE UNIT PLUMBING FIXTURES MAY EXCEED
 50 FT. FROM THE HOT WATER SOURCES- SEC. 607.2 FBC P.
 PLEASE REVIEW AND CORRECT OIF NECESSARY.
  
 41) P3.13.0: A MEANS OF DILUTING OR NEUTRALIZING THE
 CONDENSATE WASTE FROM THE GAS-FIRED WATER HEATERS IS
 REQUIRED- SEC. 803.1 FBC P.
  
 42) P0.0.1 & P5.0.1: PROVIDE PIPING SPECIFICATIONS FOR
 WATER, SANITARY, GREASE, OIL, VENT, GAS AND COMPLETE
 FIRESTOPPING DETAILS FOR WALL AND FLOOR PENETRATIONS-
 SECS. 315.1 605.4, 702.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  