2023-07-22 11:35:07PLAN DENIED
 1) PAGE SP.0.1 UNDERGROUND FUEL TANKS AND FUEL PIPING
 REQUIRE SEPRATE APPLICATION, PLAN AND PERMIT. SECTION
 1301
 FUEL PIPING AND STORAGE. 2020 FBC (M)
 2) PROVIDE THE DUCT SIZE IN RATED SHAFT FOR SMOKE
 EXHAUST
 OUT SIDE AIR AND ELEAATOR1, 2, 3, AND 4 SECTION 107 FBC
 3) PAGE M3.10.2 PROVIDE DUCT SIZE FOR DININGROOM ON
 PLAN
 SECTION 107
 4) PROVIDE CLOTHES DRYER SPECIFICSTIONS FOR THE
 APARTMENTS
 SECTION 504 CLOTHES DRYER EXHAUST. 2020 FBC (M)
 5) SHOW ON THE PLAN WHERE THE AIR CONDITIONING
 CONDENSERS
 ARE LOCATED FROM 1ST FLOOR TO 6TH FLOOR. SECTION 107
 FBC
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561805-6676