Plan Review Notes For Permit 23060501 |
Permit Number |
23060501 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-07-22 11:35:07 | PLAN DENIED | | 1) PAGE SP.0.1 UNDERGROUND FUEL TANKS AND FUEL PIPING | | REQUIRE SEPRATE APPLICATION, PLAN AND PERMIT. SECTION | | 1301 | | FUEL PIPING AND STORAGE. 2020 FBC (M) | | 2) PROVIDE THE DUCT SIZE IN RATED SHAFT FOR SMOKE | | EXHAUST | | OUT SIDE AIR AND ELEAATOR1, 2, 3, AND 4 SECTION 107 FBC | | 3) PAGE M3.10.2 PROVIDE DUCT SIZE FOR DININGROOM ON | | PLAN | | SECTION 107 | | 4) PROVIDE CLOTHES DRYER SPECIFICSTIONS FOR THE | | APARTMENTS | | SECTION 504 CLOTHES DRYER EXHAUST. 2020 FBC (M) | | 5) SHOW ON THE PLAN WHERE THE AIR CONDITIONING | | CONDENSERS | | ARE LOCATED FROM 1ST FLOOR TO 6TH FLOOR. SECTION 107 | | FBC | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561805-6676 |
|