2023-07-14 17:39:14 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 23060501 |
| 7/14/23 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P3.13.0 GAS RISER: BASED ON THE GAS PIPE |
| SIZING TABLE SPECIFIED ON THE PLAN- (402.4(3) FBC FG)- |
| THE 1-1/4-INCH SCHEDULE 40 PIPING IS UNDERSIZED TO |
| SUPPLY THE TOTAL 1,200,000 BTU LOAD AT A TOTAL |
| DEVELOPED LENGTH OF 410 FT. BASED ON THE TABLE THE |
| MINIMUM PIPE SIZE FOR THE LOAD IS 2-INCH. PLEASE NOTE |
| AN 1-1/4 PIPE IS ADEQUATE FOR A 2 PSI SYSTEM SIZED |
| ACCORDING TO TABLE 402.4(5) FBC FG. |
| |
| 2) P3.13.0 GAS RISER: PROVIDE AND ENLARGED GAS TRAIN |
| DETAIL FOR THE WATER HEATERS SHOWING THE INPUT |
| PRESSURES OF THE WATER HEATERS, LOCATIONS OF SHUT OFF |
| VALVES, REGULATORS, PIPE UNIONS, AND TEST TEES- SEC. |
| 409.1 & 410.2 FBC FG. |
| |
| A) PROVIDE THE MAKE AND MODEL OF THE SELECTED REGULATOR |
| ON THE DRAWING AND PROVIDE VENTING DETAILS INCLUDING |
| VENT PIPING RUNS AND TERMINATION LOCATIONS- SEC. 410.2 |
| & 410.3 FBC FG |
| |
| 3) P3.13.0, A2.01, & M2.01: PLEASE SHOW THE CLEARANCE |
| DISTANCES FROM THE WATER HEATER EXHAUST OUTLET TO THE |
| COMBUSTION AIR INTAKE AND OTHER GRAVITY OR MECHANICAL |
| AIR INTAKES INTO THE BUILDING- SEC. & TABLE 503.8 FBC |
| FG, AND SEC. 401.4 FBC M. |
| |
| 4) P3.13.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| THE WATER HEATERS AND INSTALLATION GUIDELINES FOR THE |
| COMBUSTION AIR AND VENT DUCTS- SEC. 624.1 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |