2023-07-13 12:52:55I WOULD LIKE TO START THIS REVIEW BY COMPLIMENTING THE
 ENGINEERS AND STAFF WHO CONTRIBUTED TO A LARGE AND
 COMPLICATED PROJECT. THESE ELECTRICAL PLANS APPEAR TO
 HAVE BEEN CAREFULLY PUT TOGETHER, WITH GREAT THOUGHT
 AND ATTENTION TO DETAIL AND THE ELECTRICAL CODES. I
 HAVE ONLY SOME MINOR COMMENTS ON CODE COMPLIANCE AND
 ADDITIONAL INFORMATION REQUIRED FOR THIS SUBMITTAL. I
 HAVE OUTLINED THESE BELOW.
  
 1) FAULT CURRENT CALCULATIONS AND SELECTIVE
 COORDINATION STUDIES BY THE NATURE OF THEIR PURPOSE
 SHOULD BE PROVIDED BEFORE SELECTING AND INSTALLING
 EQUIPMENT FOR ELECTRICAL PROJECTS. PLEASE PROVIDE THE
 APPROPRIATE AVAILABLE FAULT CURRENT SUPPLIED BY THE
 UTILITY AND THE RESULTING FAULT CURRENT CALCULATIONS AS
 REQUIRED PER NEC 110.10 AND A NOTE STATING FIELD
 MARKING TO BE DONE IN ACCORDANCE WITH NEC110.24. IN
 ADDITION, PLEASE PROVIDE STAMPED SELECTIVE COORDINATION
 STUDY IN ACCORDANCE WITH NEC 700.32 FOR THE EMERGENCY
 STANDBY SYSTEM.
  
 2) SHEET E1.1.3A DETAILS A NOTE 7 ON STATES THERE WILL
 BE AN EPO PUSHBUTTON WIRED TO ALL MAIN BREAKERS TO
 PROVIDE BUILDING WIDE SHUTDOWN OF POWER. THE RISER
 DIAGRAMS AND PANEL SCHEDULES SUBMITTED ONLY DETAIL
 SHUNT TRIP BREAKER ON PANEL OSDP. IF SHUNT TRIP
 BREAKERS ARE TO BE INSTALLED AS STATED IN NOTE, PLEASE
 DETAIL THEM ON ALL RISER DIAGRAMS AND PANEL SCHEDULES
 AS APPLICABLE. NEC 215.5
  
 3) SHEET E1.6.2B DETAILS A 50-AMP RECEPTACLE FOR A
 MULTI COOKER. PLEASE DETAIL THIS RECEPTACLE AS BEING
 GFIC PROTECTED IN ACCORDANCE WITH NEC 210.8
  
 4) SHEET E3.2.2 DETAILS WHAT APPEARS TO BE A FLOOR TO
 CEILING WINDOW IN THE LOFT ROOM WITH A LENGTH OF
 APPROXIMATELY 24 FEET. PLEASE DETAIL THE REQUIRED FLOOR
 OR WALL RECEPTACLES IN ACCORDANCE WITH NEC 210.52
  
 5) ALL SHEETS DETAILING PATIO KITCHENS APPEAR TO HAVE
 ONLY ONE SMALL APPLIANCE RECEPTACLE CIRCUIT SUPPLYING
 THE COUNTERTOP RECEPTACLES. THE REQUIREMENT IN
 ACCORDANCE WITH NEC 210.52(B)(3) IS TO HAVE TWO SMALL
 APPLIANCE CIRCUITS TO FEED THESE COUNTERTOP
 RECEPTACLES. PLEASE CORRECT AS APPLICABLE.
  
 6) ALL RESIDENTIAL UNIT???S DETAIL REFRIGERATION AND
 FREEZER RECEPTACLE BRANCH CIRCUITS SUPPLIED FROM AN
 OPTIONAL STANDBY PANEL NOT LOCATED IN THE RESIDENTIAL
 PREMISE. PLEASE PROVIDE CLARITY ON HOW THIS IS
 COMPLIANT IN ACCORDANCE WITH NEC 240.24(B). DO
 OCCUPANTS HAVE READY ACCESS TO ELECTRIC ROOMS AND READY
 ACCESS TO FLOORS OTHER THAN WHERE THEY RESIDE?
  
 NEC 240.24 (B) OCCUPANCY. EACH OCCUPANT SHALL HAVE
 READY ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE
 CONDUCTORS SUPPLYING THAT OCCUPANCY, UNLESS OTHERWISE
 PERMITTED IN 240.24(B)(1) AND (B)???(2).
  
  PLEASE BE AWARE THAT MANY LOW VOLTAGE AND OTHER TYPES
 OF WIRING ARE NOT INCLUDED WITH THIS PERMIT AND REQUIRE
 SEPARATE PERMITS. EXAMPLES OF WIRING SYSTEMS AND OTHER
 ITEMS REQUIRING SEPARATE PERMITS INCLUDE BUT ARE NOT
 LIMITED TO, LOW VOLTAGE WIRING SYSTEMS SUCH AS DAS/BDA,
 FIRE ALARM, SECURITY, AUDIO, VIDEO, VOICE, DATA,
 ACCESS, AND POOLS, SIGNS, GENERATORS, LANDSCAPE
 LIGHTING AND LIGHTNING PROTECTION.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER