2023-07-13 12:52:55 | I WOULD LIKE TO START THIS REVIEW BY COMPLIMENTING THE |
| ENGINEERS AND STAFF WHO CONTRIBUTED TO A LARGE AND |
| COMPLICATED PROJECT. THESE ELECTRICAL PLANS APPEAR TO |
| HAVE BEEN CAREFULLY PUT TOGETHER, WITH GREAT THOUGHT |
| AND ATTENTION TO DETAIL AND THE ELECTRICAL CODES. I |
| HAVE ONLY SOME MINOR COMMENTS ON CODE COMPLIANCE AND |
| ADDITIONAL INFORMATION REQUIRED FOR THIS SUBMITTAL. I |
| HAVE OUTLINED THESE BELOW. |
| |
| 1) FAULT CURRENT CALCULATIONS AND SELECTIVE |
| COORDINATION STUDIES BY THE NATURE OF THEIR PURPOSE |
| SHOULD BE PROVIDED BEFORE SELECTING AND INSTALLING |
| EQUIPMENT FOR ELECTRICAL PROJECTS. PLEASE PROVIDE THE |
| APPROPRIATE AVAILABLE FAULT CURRENT SUPPLIED BY THE |
| UTILITY AND THE RESULTING FAULT CURRENT CALCULATIONS AS |
| REQUIRED PER NEC 110.10 AND A NOTE STATING FIELD |
| MARKING TO BE DONE IN ACCORDANCE WITH NEC110.24. IN |
| ADDITION, PLEASE PROVIDE STAMPED SELECTIVE COORDINATION |
| STUDY IN ACCORDANCE WITH NEC 700.32 FOR THE EMERGENCY |
| STANDBY SYSTEM. |
| |
| 2) SHEET E1.1.3A DETAILS A NOTE 7 ON STATES THERE WILL |
| BE AN EPO PUSHBUTTON WIRED TO ALL MAIN BREAKERS TO |
| PROVIDE BUILDING WIDE SHUTDOWN OF POWER. THE RISER |
| DIAGRAMS AND PANEL SCHEDULES SUBMITTED ONLY DETAIL |
| SHUNT TRIP BREAKER ON PANEL OSDP. IF SHUNT TRIP |
| BREAKERS ARE TO BE INSTALLED AS STATED IN NOTE, PLEASE |
| DETAIL THEM ON ALL RISER DIAGRAMS AND PANEL SCHEDULES |
| AS APPLICABLE. NEC 215.5 |
| |
| 3) SHEET E1.6.2B DETAILS A 50-AMP RECEPTACLE FOR A |
| MULTI COOKER. PLEASE DETAIL THIS RECEPTACLE AS BEING |
| GFIC PROTECTED IN ACCORDANCE WITH NEC 210.8 |
| |
| 4) SHEET E3.2.2 DETAILS WHAT APPEARS TO BE A FLOOR TO |
| CEILING WINDOW IN THE LOFT ROOM WITH A LENGTH OF |
| APPROXIMATELY 24 FEET. PLEASE DETAIL THE REQUIRED FLOOR |
| OR WALL RECEPTACLES IN ACCORDANCE WITH NEC 210.52 |
| |
| 5) ALL SHEETS DETAILING PATIO KITCHENS APPEAR TO HAVE |
| ONLY ONE SMALL APPLIANCE RECEPTACLE CIRCUIT SUPPLYING |
| THE COUNTERTOP RECEPTACLES. THE REQUIREMENT IN |
| ACCORDANCE WITH NEC 210.52(B)(3) IS TO HAVE TWO SMALL |
| APPLIANCE CIRCUITS TO FEED THESE COUNTERTOP |
| RECEPTACLES. PLEASE CORRECT AS APPLICABLE. |
| |
| 6) ALL RESIDENTIAL UNIT???S DETAIL REFRIGERATION AND |
| FREEZER RECEPTACLE BRANCH CIRCUITS SUPPLIED FROM AN |
| OPTIONAL STANDBY PANEL NOT LOCATED IN THE RESIDENTIAL |
| PREMISE. PLEASE PROVIDE CLARITY ON HOW THIS IS |
| COMPLIANT IN ACCORDANCE WITH NEC 240.24(B). DO |
| OCCUPANTS HAVE READY ACCESS TO ELECTRIC ROOMS AND READY |
| ACCESS TO FLOORS OTHER THAN WHERE THEY RESIDE? |
| |
| NEC 240.24 (B) OCCUPANCY. EACH OCCUPANT SHALL HAVE |
| READY ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE |
| CONDUCTORS SUPPLYING THAT OCCUPANCY, UNLESS OTHERWISE |
| PERMITTED IN 240.24(B)(1) AND (B)???(2). |
| |
| PLEASE BE AWARE THAT MANY LOW VOLTAGE AND OTHER TYPES |
| OF WIRING ARE NOT INCLUDED WITH THIS PERMIT AND REQUIRE |
| SEPARATE PERMITS. EXAMPLES OF WIRING SYSTEMS AND OTHER |
| ITEMS REQUIRING SEPARATE PERMITS INCLUDE BUT ARE NOT |
| LIMITED TO, LOW VOLTAGE WIRING SYSTEMS SUCH AS DAS/BDA, |
| FIRE ALARM, SECURITY, AUDIO, VIDEO, VOICE, DATA, |
| ACCESS, AND POOLS, SIGNS, GENERATORS, LANDSCAPE |
| LIGHTING AND LIGHTNING PROTECTION. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |
| |