2023-07-06 11:48:35 | THE APPLICANT HAS PROVIDED AN EMAIL STATING PORCELAIN |
| TILE. |
| |
| PASSED BY FIRE 7/24/23 |
| |
| PML |
| |
| ******************************************************* |
| ***************************************************** |
| |
| |
| |
| |
| THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE ARE INDICATIONS OF TILE FLOOR ON THE |
| APPLICATION, HOWEVER, NO SPEC SHEET NOR A PRODUCT NAME |
| FOR THE ACTUAL PROPOSED TILE FLOORING. |
| |
| TILE FLOORING CAN HAVE DIFFERENT MEANINGS AND CAN BE |
| MANUFACTURED AROUND THE WORLD BUT NOT ALL ARE TESTED |
| AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| THE CLASSES SPECIFIED |
| IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| CRITICAL RADIANT FLUX |
| REQUIREMENTS. |
| 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| 0.45 W/CM2, AS DETERMINED |
| BY THE TEST DESCRIBED IN 10.2.7.3. |
| 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| 0.22 W/CM2, BUT LESS |
| THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| 10.2.7.3. |
| |
| FOR CLARIFICATION AND FOR THE OFFICIAL RECORD, PLEASE |
| PROVIDE THE TILE FLOORING TYPE, PRODUCT NAME AND, IF |
| APPLICABLE, THE PRODUCT SPEC SHEETS INDICATING THE FIRE |
| BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED, BUT NEEDS TO BE INDICATED ON THE |
| PLAN. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |