Plan Review Notes
Plan Review Notes For Permit 23060402
Permit Number 23060402
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-23 10:54:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF FLOORING ON THE
 APPLICATION, HOWEVER, IT IS NOT CLEAR WHERE THE
 FLOORING WILL BE INSTALLED, WHAT TYPE OF FLOORING NOR
 SPECIFICATION SHEETS.
  
 THERE IS ALSO NO INDICATION OF SOUND UNDERLAYMENT NOR
 THE SPEC SHEET FOR THE FLOOR UNDERLAYMENT.
  
 THERE ARE MANY TYPES OF FLOORING AND HAVE DIFFERENT
 MEANINGS AND CAN BE MANUFACTURED AROUND THE WORLD BUT
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE
 FLOORING TYPE, PRODUCT NAME, WHERE IT WILL BE INSTALLED
 AND, IF APPLICABLE, THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED, BUT NEEDS TO BE INDICATED ON THE
 PLAN.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  