Plan Review Notes
Plan Review Notes For Permit 23060367
Permit Number 23060367
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-21 12:57:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS ON THE COVER SHEETUNDER THE
 GENERAL SECTION OF NUMBERED PLAN SHEETS THAT ARE NOT
 ATTACHED TO THE SUBMITTAL PACKAGE.
  
 THERE IS NO SCOPE OF WORK NOR ANY DETAILED PLAN SHEETS
 ON WHAT IS EXISTING OR WHAT IS NEW.
  
 MISSING ARE ID-000, ID-001, ID-100, ID-103, E-2, E-3,
 M-2, P-2, S-1 & S-2.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED PLAN SHEETS AND
 DETAILS TO CONDUCT A THOUROUGH LIFE SAFETY REVIEW OF
 THE PROPOSED WORK.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  