2023-06-22 14:11:161ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 406.2 - THE SANITARY ISOMETRIC SHOWS AN 1
 1/2" STANDPIPE TO THE WASHING MACHINE. A 2" IS
 REQUIRED.
  
 2. WPB ORD. SEC. 90 - 126 - PLEASE SHOW A DETAIL THAT
 INCLUDE THE DISCHARGE LOCATION OF THE AC CONDENSATE
 DRAIN TO VERIFY IT DOES NOT GO INTO THE SANITARY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  