Plan Review Notes
Plan Review Notes For Permit 23060362
Permit Number 23060362
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-21 13:39:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE SUBMITTED PLANS; HOWEVER, THERE ARE NO
 DETAILS ON THESE PLANS TO REVIEW FOR LIFE SAFETY CODE
 COMPLIANCE.
  
 THERE IS NO SCOPE OF WORK NOR ANY DETAILED PLAN SHEETS
 ON WHAT IS EXISTING OR WHAT IS NEW.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED PLAN SHEETS AND
 DETAILS TO CONDUCT A THOROUGH LIFE SAFETY REVIEW OF THE
 PROPOSED WORK.
  
  
 1A.) PLAN SHEETS ID-101, ID-102, ID-103, ID-104 & 105
 ARE MISSING.
  
 PLEASE REVIEW AND SUBMIT OR CORRECT THE COVER SHEET
 LIST.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]