Date |
Text |
2023-06-12 10:33:20 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. PLEASE VERIFY & CORRECT; MASTER ROOF |
| PLAN DRAWING SHEET A4-1 SPECIFICATIONS CALLS FOR A |
| 4-PLY BUILT-UP ROOFING SYSTEM. PROVIDE A COMPLETE SET |
| OF 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE |
| PROPOSED FLAT ROOF SYSTEM TO BE USED. INCLUDE COVER |
| PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS |
| FOR SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| ENGINEERING. PROJECT LOCATED IN EXPOSURE D CATEGORY |
| AREA. |
| 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| 17-0406.02HAS EXPIRED AND IS NO LONGER VALID. PROVIDE A |
| COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED ROOF WATERPROOFING |
| SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND |
| ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING |
| 3. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| SUBMITTING. REVIEW STAMP WITH INITIALS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |