Plan Review Notes
Plan Review Notes For Permit 23060319
Permit Number 23060319
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-09 12:13:41FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED
 CODE: 603
  
 TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS CHARGED/
 DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL FOR
 LEAKS
 & INSPECTOR DRAIN AFTER 2 HRS)
  
  
 PETER LEDUC
 FIRE MARSHAL