2023-07-07 15:20:29 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| NFPA 70 2017 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| OUTLETS IN THE KITCHEN AND WITHIN 6" OF THE SINKS TO BE |
| GFCI PROTECTED |
| |
| POS 5,11 |
| PANEL A-4,39,2,33,31,29,27,23,25 |
| PANEL B-37,6,4,17,28,16,26 |
| PANEL C-17 |
| PANEL D-2,37,31,25,36,19,13,7,1 |
| PANEL E-19,8,2,10,31,32,46 |
| PANEL F-26, 24,22,27,29,14 |
| PANEL G-6,10,12,14,8,41,2,37,5,13,3,9,23,6,35,14,41 |
| |
| 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL. |
| |
| GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL SHALL BE PROVIDED AS REQUIRED IN 210.8(A) |
| THROUGH (E). THE GROUND-FAULT CIRCUIT INTERRUPTER SHALL |
| BE INSTALLED IN A READILY ACCESSIBLE LOCATION. |
| (B) OTHER THAN DWELLING UNITS. |
| ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND |
| OR LESS, 50 AMPERES OR LESS AND THREE-PHASE RECEPTACLES |
| RATED 150 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS |
| INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE |
| GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL. |
| |
| (2) |
| KITCHENS |
| |
| (5) |
| SINKS ??? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M |
| (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE SINK |
| EXCEPTION NO. 1 TO (5): IN INDUSTRIAL LABORATORIES, |
| RECEPTACLES USED TO SUPPLY EQUIPMENT WHERE REMOVAL OF |
| POWER WOULD INTRODUCE A GREATER HAZARD SHALL BE |
| PERMITTED TO BE INSTALLED WITHOUT GFCI PROTECTION. |
| |
| EXCEPTION NO. 2 TO (5): FOR RECEPTACLES LOCATED IN |
| PATIENT BED LOCATIONS OF GENERAL CARE (CATEGORY 2) OR |
| CRITICAL CARE (CATEGORY 1) SPACES OF HEALTH CARE |
| FACILITIES OTHER THAN THOSE COVERED UNDER 210.8(B)(1), |
| GFCI PROTECTION SHALL NOT BE REQUIRED. |
| |