2023-07-07 15:20:29FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 OUTLETS IN THE KITCHEN AND WITHIN 6" OF THE SINKS TO BE
 GFCI PROTECTED
  
 POS 5,11
 PANEL A-4,39,2,33,31,29,27,23,25
 PANEL B-37,6,4,17,28,16,26
 PANEL C-17
 PANEL D-2,37,31,25,36,19,13,7,1
 PANEL E-19,8,2,10,31,32,46
 PANEL F-26, 24,22,27,29,14
 PANEL G-6,10,12,14,8,41,2,37,5,13,3,9,23,6,35,14,41
  
 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL SHALL BE PROVIDED AS REQUIRED IN 210.8(A)
 THROUGH (E). THE GROUND-FAULT CIRCUIT INTERRUPTER SHALL
 BE INSTALLED IN A READILY ACCESSIBLE LOCATION.
 (B) OTHER THAN DWELLING UNITS.
 ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND
 OR LESS, 50 AMPERES OR LESS AND THREE-PHASE RECEPTACLES
 RATED 150 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS
 INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 (2)
 KITCHENS
  
 (5)
 SINKS ??? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M
 (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE SINK
 EXCEPTION NO. 1 TO (5): IN INDUSTRIAL LABORATORIES,
 RECEPTACLES USED TO SUPPLY EQUIPMENT WHERE REMOVAL OF
 POWER WOULD INTRODUCE A GREATER HAZARD SHALL BE
 PERMITTED TO BE INSTALLED WITHOUT GFCI PROTECTION.
  
 EXCEPTION NO. 2 TO (5): FOR RECEPTACLES LOCATED IN
 PATIENT BED LOCATIONS OF GENERAL CARE (CATEGORY 2) OR
 CRITICAL CARE (CATEGORY 1) SPACES OF HEALTH CARE
 FACILITIES OTHER THAN THOSE COVERED UNDER 210.8(B)(1),
 GFCI PROTECTION SHALL NOT BE REQUIRED.
  