Notes
Date Text
2023-07-12 16:17:04PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC - R 301.2.1.2 SUBMIT AN INSTALLATION SCHEDULE AND
 KEY PLAN FOR THE STORM PANELS. SPECIFY THE OPENING
 SIZE, THE WIND PRESSURES, TYPE OF ANCHOR, ANCHOR
 SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL SPAN,
 SEPARATION DISTANCE FROM PANEL TO GLASS AND THE
 APPLICABLE SECTION NUMBER FROM THE INSTALLATION
 DRAWINGS/PRODUCT APPROVAL.