Plan Review Notes
Plan Review Notes For Permit 23060200
Permit Number 23060200
Review Stop B
Sequence Number 2
Notes
Date Text
2023-06-14 15:32:33ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE FLAT DECK
 ROOFING SYSTEM - PRODUCT APPROVAL FOR THE FLAT DECK
 ROOFING = NEED TO CHOOSE A ROOFING SYSTEM IN THE
 PRODUCT APPROVAL THAT SHOWS THE REQUIRED WIND DESIGN
 PRESSURE PER FBC R TABLE R301.2(2) - PLEASE CIRCLE THE
 ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL - IF
 NEEDED PLEASE PROVIDE ADDITIONAL ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND
 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE THEN THE
 CHOSEN ROOFING SYSTEM - SEE NOTES ON THE PRODUCT
 APPROVAL.