2023-06-28 12:42:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS INSUFFICIENT DETAIL REGARDING THE SPECIFIC | | LOCATION OF THE PROPOSED GRILLS AND HOW MANY GRILLS ARE | | PROPOSED. | | | | PER NFPA 1 | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | APPLICABLE CODES AND STANDARDS | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE GREATER DETAIL | | OF EACH AREA OF THE PROPOSED GRILL, INDICATING IT IS A | | MIN. OF 10' FROM COMBUSTILES, NOT UNDER A COMBUSTIBLE | | ROOF AND NOT IMPEDING A PATH OF EXIT. | | | | | | 1A) THERE IS AN INDICATION OF PROPANE GRILLS, HOWEVER, | | THERE IS NO INDICATION OF WHERE SPARE FULL OR EMPTY | | TANKS WILL BE STORED. | | | | PLEASE PROVIDE A DETAIL NARRATIVE OR ADDITIONAL SITE | | LOCATION PROPOSED FOR STORAGE AND MAINTENCE OF THE | | TANKS PER NFPA 1 CH 66 & NFPA 58. | | | | TANKS CAN NOT BE STORED WITHIN THE BUILDING. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|