Plan Review Notes For Permit 23060123 |
Permit Number |
23060123 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-06-09 10:16:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION OF UPGRADE OF A FA SYSTEM. | | | | THERE IS NO INDICATION OF THE FA OF THE CORE BUILDING | | AND IF THIS FA COMMUNICATES WITH THAT FA. | | | | PER NFPA 72 23.8.2.1 AND 23.8.2.2 | | | | 23.8.2.1 FIRE ALARM SYSTEMS SHALL BE PERMITTED TO | | COMBINE ALL DETECTION, NOTIFICATION, AND AUXILIARY | | FUNCTIONS IN A SINGLE SYSTEM OR BE A COMBINATION OF | | COMPONENT SUBSYSTEMS. | | 23.8.2.2 EXCEPT AS PERMITTED IN 23.8.2.3, THE FIRE | | ALARM SYSTEMS COMPONENTS SHALL BE PERMITTED | | TO SHARE CONTROL EQUIPMENT OR SHALL BE ABLE TO OPERATE | | AS STAND-ALONE SUBSYSTEMS, BUT SHALL | | BE ARRANGED TO FUNCTION AS A SINGLE SYSTEM IN | | ACCORDANCE WITH 23.8.2.4 THROUGH 23.8.2.10 | | | | PLEASE REVIEW AND PROVIDE A DETAILED NARRATIVE AND | | PROVIDE CODE REFERENCES THAT SAYS IT IS NOT REQUIRED TO | | COMMUNICATE WITH THAT FA. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|