2023-06-28 11:21:12 | ELECTRIC REVIEW FAILED |
| |
| 1) LINE DIAGRAM STATES METER TO BE REPLACED AND MSP TO |
| BE RELOCATED , HOWEVER SITE DIAGRAM DETAILING THIS |
| EQUIPMENT HAS NOT CHANGED LOCATION. PLEASE PROVIDE A |
| SITE PLAN DETAILING LOCATIONS FOR ALL EQUIPMENT AS PER |
| REVISION. FBC 107.2 |
| |
| FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL |
| |
| 2) REVISION APPLICATION STATES VALUE OF WORK AS $0. |
| PLEASE PROVIDE A CORRECT VALUE FOR THE ADDITIONAL WORK. |
| WPB F.B.C. 109.3 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |