2023-06-06 10:45:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF A 10 X 30 CHICKEE HUT W NO |
| ELECTIC NOR PLUMBING; HOWEVER, THERE IS NO INDICATED |
| PURPOSE NOR USE OF THE PROPOSED. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE OCCUPANCY |
| CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE AND |
| ANY APPLICABLE FLOOR PLANS INCLUDING |
| TABLES/CHAIRS, FURNITURE, PLANTERS, LANDCAPE, ETC. |
| UNDER IT. |
| |
| |
| |
| 2) THERE IS AN INDICATION ON THE SURVEY OF THE HUT 5 ' |
| FROM THE EAST BUILDING AND WHAT APPEARS TO BE LESS FROM |
| THE EXISTING SITE BUILDING BUT NO INDICATION HOW THIS |
| PROPOSED LOCATION AFFECTS THE EXISTING EXITING OF THE |
| EXISTING BUILDING. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| |
| PLEASE PROVIDE A LIFE SAFETY PLAN SHEET INDICATING |
| COMPLIANCE |
| |
| |
| |
| 3) THERE IS AN INDICATION OF AN APPARENT COMBUSTIBLE |
| VEGETATION HUT, BUT NO INDICATION OF PROPOSED FIRE |
| PROTECTION/FIRE RETARDANT CERTIFICATION. |
| |
| 4.6 GENERAL REQUIREMENTS |
| |
| 4.6.1 AUTHORITY HAVING JURISDICTION. |
| |
| 4.6.1.1 THE AUTHORITY HAVING JURISDICTION SHALL |
| DETERMINE WHETHER THE |
| PROVISIONS OF THIS CODE ARE MET. |
| |
| 4.6.1.2 ANY REQUIREMENTS THAT ARE ESSENTIAL FOR THE |
| SAFETY OF BUILDING |
| OCCUPANTS AND THAT ARE NOT SPECIFICALLY PROVIDED FOR BY |
| THIS CODE SHALL |
| BE DETERMINED BY THE AUTHORITY HAVING JURISDICTION |
| |
| 4.6.1.3 WHERE IT IS EVIDENT THAT A REASONABLE DEGREE OF |
| SAFETY IS PROVIDED, |
| ANY REQUIREMENT SHALL BE PERMITTED TO BE MODIFIED IF, |
| IN THE JUDGMENT |
| OF THE AUTHORITY HAVING JURISDICTION, ITS APPLICATION |
| WOULD BE HAZARDOUS |
| UNDER NORMAL OCCUPANCY CONDITIONS. |
| |
| PLEASE PROVIDE FOR THE INTENT TO APPLY/INSTALL A FIRE |
| RETARDANT CERTICATION BY A QUALIFIED LICENSED CONTRATOR |
| TO THIS STRUCTURE. |
| |
| |
| |
| 4) FOR INFORMATIONAL PURPOSES; |
| |
| NO COOKING, BBQS, OPEN FLAMES NOR PROPANE HEATERS WILL |
| BE ALLOWED UNDER THE HUT WITHOUT PRIOR REVIEW AND |
| APPROVAL |
| AND/OR PERMITTING IF APPLICABLE. |
| |
| WARMING OF FOOD IS ACCEPTABLE, ENSURE NO COMBUSTIBLES |
| NEAR WARMING DEVICES. |
| |
| NO PYROTECHNICS/FLAME EFFECTS ON STAGE IN OR AROUND THE |
| HUT WITHOUT PROPER FIREWORKS APPLICATION |
| APPROVAL BY THE FIRE MARSHAL. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |