Plan Review Notes For Permit 23051624
Permit Number 23051624
Review Stop P
Sequence Number 1
Notes
Date Text
2023-06-07 09:59:361ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051624
 6/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY EFFICIENCY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR, AT A MINIMUM, THE PERMIT APPLICATION FOR
 SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING PLAN
 APPROVAL. IF A CONTRACTOR IS NOT CURRENTLY SELECTED THE
 INSTALLATION, A PERMIT APPLICATION CAN BE SUBMITTED TBD
 (TO BE DETERMINED). THE COMPLETED APPLICATION SHALL BE
 EMAILED TO [email protected] . YOU WILL THEN
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEETS P0.2, P0.3, P0.5, P0.6, P1.1A, P1.1B: REFER
 TO SEC. 1003.3.1 FBC P- GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED. THE PLANS SHOW DRAINAGE
 FROM FIXTURES SUCH AS HAND SINKS, FLOOR SINKS UNDER ICE
 MACHINES, AND COOLER EVAPORATORS DISCHARGING INTO THE
 GREASE WASTE LINE. PLEASE RE-ROUTE THE DRAINAGE FROM
 THE FIXTURES LISTED BELOW TO THE SANITARY SYSTEM:
 HAND SINKS- A61, A77, B14, B33, B43
 FLOOR SINKS RECEIVING DRAINAGE FROM B43, B43.1, B43.2,
 B48.2, B53.2.
  
 3) P0.2: BASED ON COMMENT #1 ABOVE THE HAND SINKS SHALL
 BE REMOVED FROM THE GREASE WASTE CALCULATIONS- SEC.
 1003.3.1 FBC P.
  
 4) P2.1A, P2.1B: FOR CLARIFY PLEASE NOTE THE LOCATIONS
 OF THE WATER HEATERS USING THE NUMBER 9 PER THE NOTES
 ON THE PLANS- SEC. 107.2.1 WPB.
  
 5) P0.1 & P0.2: BASED ON SEC. 607.1.1 FBC P,
 TEMPERATURE LIMITING DEVICES SHALL BE PROVIDED FOR THE
 NEW WATER HEATERS. TYPICALLY A MASTER THERMOSTATIC
 MIXING VALVE CAN BE INSTALLED TO MEET COMPLIANCE.
 PLEAASE SHOW THE DEVICE IN THE DETAIL AND PIPING
 CONNECTIONS.
  
 6) P0.2, P2.1A, & P2.1B: PLEASE SHOW THE BATHROOM
 FIXTURE WATER SUPPLY LINES POINTS OF CONNECTIONS TO THE
 NEW BRANCH WATER LINES- SEC. 107.2.1 WPB.
  
 7) A2.1: PLEASE SHOW THE DIMENSIONS OF THE WATER CLOSET
 AND LAVATORY CLEAR FLOOR SPACES AS REQUIRED BY SECS.
 604.3 & 606.2 FBC ACC. BASED ON THE MALE AND FEMALE
 ACCESSIBLE STALL WIDTHS SHOWN ON THE PLANS, IT APPEARS
 THE CLEAR FLOOR SPACES REQUIRED FOR THE WATER CLOSETS
 WILL BE OVERLAPPING THE LAVATORIES WHICH IS NOT ALLOWED
 PER SEC. 604.3.2.
  
 8) A2.1: PLEASE SHOW THE HEIGHTS OF THE GRAB BARS
 MEASURED FROM THE FINISHED FLOORS TO THE TOPS OF THE
 BAR GRIPPING SURFACES- SEC. 609.4 FBC ACC.
  
 9) A2.1: PLEASE SHOW THE ADA LAVATORY KNEE CLEARANCE
 WILL BE 11 INCHES DEEP MINIMUM AT 9 INCHES ABOVE THE
 FINISH FLOOR OR GROUND, AND 8 INCHES DEEP MINIMUM AT 27
 INCHES ABOVE THE FINISH FLOOR OR GROUND.
  
 10) PLEASE ADD THE ENERGY COMPLIANCE DATA FOR THE WATER
 HEATERS TO THE ENERGYGAUGE REPORT- SEC. C101.5 & TABLE
 C404.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  