Date |
Text |
2023-06-01 14:54:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET A0.2 & A2.0- THERE ARE INDICATIONS OF A SINGLE |
| DOOR ALONG THE FRONT FENCE OF THE SIDE YEARD OUTSIDE |
| SEATING AREA. THE DOOR IS INDICATED AS SWINGING INWARD. |
| |
| PREVIOUS APPROVED PLANS ON RECORD 16050258 SHOWED DOORS |
| SWINGING OUTWARD. |
| |
| PER NFPA 101, CH 7 MEANS OF EGRESS, |
| |
| 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| REQUIRED TO BE OF |
| THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| THE DIRECTION |
| OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| OF 50 OR MORE, |
| EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| REQUIRED TO SWING |
| IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| 7.2.4.3.8.1 |
| OR 7.2.4.3.8.2. |
| (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| TO SWING |
| IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19. |
| (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| ENCLOSURE, UNLESS THE |
| DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| OPENS DIRECTLY |
| INTO AN EXIT ENCLOSURE |
| |
| |
| (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| CONTENTS AREA |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 2) SHEET A2.0 & A5.0 - THERE ARE INDICATIONS OF |
| GATES/DOORS ON THE EXTEIOR FENCES OF THE OUTSIDE AREA |
| THAT ARE INDICATED AND REQUIRED AS EXITS. |
| |
| THE ARE NO INDICATIONS ON THE DOOR SCHEDULE OF THE EXIT |
| HARDWARE/LOCKS/LATCHES THAT ARE IN COMPLINACE WITH THE |
| REQUIREMENTS OF NFPA 101 CH 7 MEANS OF EGRESS. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 3) SHEET M1.1A - THERE ARE INDICATIONS OF NEW HOOD |
| WORK. |
| |
| ANY WORK ON THE HOOD SYSTM SHALL BE UNER SEPARATE |
| PERMIT & SHOP DRAWINGS PER NFPA 96. |
| |
| PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| ACKNOWLGMENT ON THE PLAN. |
| |
| |
| |
| 4) SHEET A0.2 & A2.0 - THE OCCUPNACY HAS AN EXISTING |
| FIRE SPRINKLER AND FIRE ALARM SYSTEM. |
| |
| THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| DEMO AND CONSTRUCTION. |
| |
| PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| EQUIPMENT. |
| |
| DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| DEVICES/EQUIPMENT. |
| |
| ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE |
| CORRECTED/REPAIRED PER NFPA 13 & 72, UNDER SEPARATE |
| PERMIT AND SHOP DRAWING BY FS/FA CONTRACTORS |
| |
| PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| NOTE OF ACKNOWLEDGMENT ON THE FLOOR & LIFE SAFETY PLAN. |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |