2023-06-01 14:54:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A0.2 & A2.0- THERE ARE INDICATIONS OF A SINGLE
 DOOR ALONG THE FRONT FENCE OF THE SIDE YEARD OUTSIDE
 SEATING AREA. THE DOOR IS INDICATED AS SWINGING INWARD.
  
 PREVIOUS APPROVED PLANS ON RECORD 16050258 SHOWED DOORS
 SWINGING OUTWARD.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS,
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
  
  
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) SHEET A2.0 & A5.0 - THERE ARE INDICATIONS OF
 GATES/DOORS ON THE EXTEIOR FENCES OF THE OUTSIDE AREA
 THAT ARE INDICATED AND REQUIRED AS EXITS.
  
 THE ARE NO INDICATIONS ON THE DOOR SCHEDULE OF THE EXIT
 HARDWARE/LOCKS/LATCHES THAT ARE IN COMPLINACE WITH THE
 REQUIREMENTS OF NFPA 101 CH 7 MEANS OF EGRESS.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET M1.1A - THERE ARE INDICATIONS OF NEW HOOD
 WORK.
  
 ANY WORK ON THE HOOD SYSTM SHALL BE UNER SEPARATE
 PERMIT & SHOP DRAWINGS PER NFPA 96.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLGMENT ON THE PLAN.
  
  
  
 4) SHEET A0.2 & A2.0 - THE OCCUPNACY HAS AN EXISTING
 FIRE SPRINKLER AND FIRE ALARM SYSTEM.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE
 CORRECTED/REPAIRED PER NFPA 13 & 72, UNDER SEPARATE
 PERMIT AND SHOP DRAWING BY FS/FA CONTRACTORS
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR & LIFE SAFETY PLAN.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  