2023-06-22 13:07:53 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FPC 912.1 - EACH WET-VENTED FIXTURE DRAIN SHALL |
| CONNECT INDEPENDENTLY TO THE HORIZONTAL WET VENT. THE |
| WATER CLOSET, TUB AND SHOWER ARE ILLEGALLY CONNECTED. |
| THEY EACH NEED TO CONNECT INDEPENDENTLY TO THE VENTED |
| BRANCH. |
| |
| 2. 2017 WPB AMENDS 107.2.1 - PLEASE CLARIFY THE VENT. |
| TYPICALLY, THE VENT WOULD TIE INTO A VENT STACK. IF |
| THIS IS ON THE TOP FLOOR AND A NEW VENT THROUGH THE |
| ROOF IS INTENDED, THEN NEW PENETRATIONS WOULD BE |
| SUBJECT TO FIRE STOPPING RULES. IF THIS IS ON THE TOP |
| FLOOR THE THE DRAIN DETAIL THAT INDICATE "UP TO THE |
| 13TH FLOOR" WOULD NOT BE THERE. IT WOULD BE A "STACK |
| VENT". |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |