2023-07-11 10:47:46 | RENOVATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) CORRIDOR AT STAIR 1, DOOR 106 - PLEASE SHOW THAT THE |
| DOOR COMPLIES WITH FBC 1005.7 ENCROACHMENT. |
| ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH |
| SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS |
| SECTION. |
| 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT |
| REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178 |
| MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE |
| REQUIRED WIDTH BY MORE THAN ONE-HALF. |
| |
| 2) PLEASE PROVIDE A SITE PLAN SHOWING THE BUILDING SET |
| BACKS - FBC 107.2.5 SITE PLAN. THE CONSTRUCTION |
| DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT |
| SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE |
| THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| WATER RETAINING SWALES) |
| |
| 3) DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE |
| PUBLIC RIGHT-OF-WAY. FBC 3202.2 |
| |
| 4) DRAWINGS T.100, LS.101, LS.102, LS.103 AND ALL OF |
| THE ARCHITECTURAL DRAWINGS NEED TO BE SIGNED AND SEALED |
| BY THE DESIGNER - FBC WPB 107.1 |
| SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| SPECIFIC TYPE OF E-SIGNATURE). |