2023-06-13 12:00:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS AN INDICATION OF A GENERATOR, HOWEVER, |
| THERE ARE NO MANUFACTURES SPEC SHEETS NOR |
| CLASSIFICATION, TYPE & LEVEL PER NFPA 110. |
| |
| CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| SYSTEMS (EPSSS) |
| |
| 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| ELECTRICAL |
| POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| LOADS FOR |
| A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| WITHIN A SPECIFIED |
| TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER |
| SUPPLY |
| AS SPECIFIED IN TABLE 4.1(B). |
| |
| 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| HOURS, FOR |
| WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| WITHOUT |
| BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| SECONDS, |
| THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| TRANSFER |
| SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| 4.1(B) |
| PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| EQUIPMENT |
| INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| OR |
| SERIOUS INJURIES. |
| 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND |
| SAFETY. |
| 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. |
| 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT |
| ALL LOADS |
| SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER |
| THAT |
| MEETS ALL THE FOLLOWING CRITERIA: |
| (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE |
| LOAD |
| (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED |
| IN TABLE |
| 4.1(A) |
| (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED |
| IN TABLE |
| 4.1(B) |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| |
| 2) THERE IS NO INDICATION OF A FUEL SOURCE. |
| |
| 7.9 FUEL SYSTEM. |
| 7.9.1 FUEL TANKS SHALL BE SIZED TO ACCOMMODATE THE |
| SPECIFIC |
| EPS CLASS. |
| 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| AND MAINTAINED |
| IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| AND USE OF |
| STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| 54, NATIONAL |
| FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| CODE |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| 2A) THERE APPEARS TO BE AN INDICATION OF NG, HOWEVER, |
| THERE ARE NO NG SUPPLY DETAILS, INCLUDING PIPING TIE-IN |
| LOCATION, SIZE, LENGTH, DEPTH DIMENSION, ETC. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| PER NFPA 54 |
| |
| CHAPTER 1 ADMINISTRATION |
| 1.1 SCOPE. |
| 1.1.1 APPLICABILITY. |
| 1.1.1.1 THIS CODE IS A SAFETY CODE THAT SHALL APPLY TO |
| THE INSTALLATION |
| OF FUEL GAS PIPING SYSTEMS, APPLIANCES, EQUIPMENT, AND |
| RELATED ACCESSORIES AS SHOWN IN 1.1.1.1(A) THROUGH |
| 1.1.1.1(D). |
| (A)* COVERAGE OF PIPING SYSTEMS SHALL EXTEND FROM THE |
| POINT OF |
| DELIVERY TO THE APPLIANCE CONNECTIONS. FOR OTHER THAN |
| UNDILUTED |
| LIQUEFIED PETROLEUM GAS (LP-GAS) SYSTEMS, THE POINT OF |
| DELIVERY SHALL BE THE OUTLET OF THE SERVICE METER |
| ASSEMBLY OR THE |
| OUTLET OF THE SERVICE REGULATOR OR SERVICE SHUTOFF |
| VALVE WHERE NO |
| METER IS PROVIDED. FOR UNDILUTED LP-GAS SYSTEMS, THE |
| POINT OF |
| DELIVERY SHALL BE CONSIDERED TO BE THE OUTLET OF THE |
| FINAL PRESSURE |
| REGULATOR, EXCLUSIVE OF LINE GAS REGULATORS WHERE NO |
| METER |
| IS INSTALLED. WHERE A METER IS INSTALLED, THE POINT OF |
| DELIVERY |
| SHALL BE THE OUTLET OF THE METER. |
| |
| IF NG IS THE FUEL SOURCE, PLEASE PROVIDE FUEL INE |
| DETAILS PER NFPA 54. |
| |
| |
| 3) THERE IS A SITE PLAN SUBMITTED, HOWEVER, THERE IS NO |
| SPECIFIC DETAIL OF THE LOCATION INCLUDING ALL |
| DIMENSIONS TO THE NEAREST BUILDINGS, WINDOW, DOORS, |
| A/C, ETC. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| PLEASE PROVIDE A DETAILED SITE PLAN. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |