2023-07-20 12:12:35 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R38 |
| HAS BEEN REVISED TO FL5259-R39. PLEASE PROVIDE A |
| COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS |
| MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE |
| UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE |
| SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS |
| FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4B |
| 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF APPLICATIONS. |
| ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SYSTEM |
| MUST MEET OR EXCEED THE MINIMUM DESIGN PRESSURE |
| REQUIREMENTS FOR A HIP ROOF; (6:12) ROOF SLOPE; MEAN |
| ROOF HEIGHT 15 FT. MINIMUM DESIGN PRESSURE REQUIREMENT |
| OF -70 IN AN EXPOSURE CATEGORY C AREA. |
| 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE TILE ADHESIVE TO BE USED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |