Review Stop B
Sequence Number 3
Notes
Date Text
2023-07-20 12:12:35JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R38
 HAS BEEN REVISED TO FL5259-R39. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS
 MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS
 FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4B
 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF APPLICATIONS.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SYSTEM
 MUST MEET OR EXCEED THE MINIMUM DESIGN PRESSURE
 REQUIREMENTS FOR A HIP ROOF; (6:12) ROOF SLOPE; MEAN
 ROOF HEIGHT 15 FT. MINIMUM DESIGN PRESSURE REQUIREMENT
 OF -70 IN AN EXPOSURE CATEGORY C AREA.
 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE TILE ADHESIVE TO BE USED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  