2023-06-15 16:16:25 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE |
| FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE |
| WASTE. HAND SINKS ARE NOT DESIGNED TO RECEIVE F.O.G. |
| AND SHALL BE DIRECTED TO THE SANITARY, NOT THE GREASE |
| WASTE. ICE MAKERS AND ICE BINS ALSO ARE TO GO TO THE |
| SANITARY AND NOT THE GREASE WASTE. |
| |
| 2. 2017 WPB AMENDS 107.2.1 - PLEASE LABEL THE PLUMBING |
| FIXTURES ON THE PLUMBING SCHEDULE TO ASSOCIATE WITH THE |
| SANITARY ISO. NOTE THAT LAVATORIES ARE ONLY IN |
| BATHROOMS. SINKS ARE IN KITCHENS. HAND SINKS ARE FOR |
| HAND WASHING ONLY. CLARIFY THE LABELS. |
| |
| 3. 2020 FPC 607.1.1 - THE ELECTRIC WATER HEATER DETAIL |
| AND THE ISOMETRIC SHOW 140 DEGREE WATER GOING TO THE |
| KITCHEN WITHOUT A MIXING VALVE. PER THIS CODE SECTION, |
| THE THERMOSTAT ON THE WATER HEATER SHALLL NOT SERVE AS |
| THE LIMITING DEVICE FOR HOT OR TEMPERED WATER DELIVERY. |
| ALL HOT WATER MUST BE LIMITED BY A MIXING DEVICE. IF |
| YOU NEED 120 DEGREE AND 140 DEGREE HOT WATER, THEN TWO |
| SEPARATE MIXING DEVICES WILL BE NEEDED. THESE DEVICES |
| NEED TO MEET THE ASSE 1017 STANDARD. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |