| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 SUBMITTED STATE OF FLORIDA PRODUCT |
| APPROVAL FL4103-R11 COVERS MULTIPLE RIDGE VENT SYSTEMS. |
| ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL35321-R1 COVERS MULTIPLE PRODUCTS & |
| INSTALLATION METHODS. SELECT PRODUCT & INSTALLATION |
| METHOD TO BE USED. ALL APPLICABLE DETAILS AND |
| ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| APPROVAL DRAWINGS. |
| 3. SUBMITTED PRODUCT APPROVAL FL27076-R/ MIAMI-DADE |
| COUNTY NOA 18-0409.06 COVERS MULTIPLE APPROVED PRODUCTS |
| & ASSEMBLIES: SYSTEMS E(1) THROUGH E(4). SELECT PRODUCT |
| & SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND |
| ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| APPROVAL DRAWINGS. |
| 4. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL2533-R29 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY. |
| 5. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |