2023-06-09 13:17:01 | 2ND REVIEW FBC-2020 RES. GAS | | PERMIT- 23051233 | | 6/9/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) GAS RISER: DUE TO THE INCREASED BTUH LOAD OF THE | | GENERATOR, THE 3/4-INCH PE PIPE MUST BE INCREASED TO | | 1-INCH FROM THE METER TO THE TEE AT THE WATER HEATER- | | TABLE G2413.8 [402.4(22)] FBC RES & FBC FG. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|