Plan Review Notes
Plan Review Notes For Permit 23051223
Permit Number 23051223
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-25 16:01:48SPOKE WITH APPLICANT 6/2/23 10:30AM, HE STATED THAT
 THEY HAVE ANY EXISTING FLOORING PERMIT 22111032 THAT
 WAS APPROVED AND IS RELATED TO THIS PERMIT AND
 SHOULD HAVE BEEN INDICATED ON THIS PERMIT.
  
 FLOORING COMMENT ADDRESSED.
  
 COMMNETS 2 & 3 WILL BE CHANGED TO PROVISO, 4 & 5 NO
 LONGER APPLY: APPLICANT ACKNOWLEDGED.
  
 FIRE PROVISO:
  
 1) THERE ARE INDICATIONS OF BATHROOM WORK THAT MAY
 INVOLVE REQUIRED NFPA FIRE RATED TENANT/CORRIDOR
 SEPARATION WALLS.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED,
 ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON
 THE PLAN SHEET.
  
  
  
 2 ) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
 *******************************************************
 *******************************************************
 ******************************
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF A FLOORING TYPE,
 MANUFACTURER'S SPECIFICATION SHEET NOR A PRODUCT NAME.
  
 FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL
 ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 TYPE THE PRODUCT ANMCE AND SPEC SHEETS INDICATING THE
 FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE ARE INDICATIONS OF BATHROOM WORK THAT MAY
 INVOLVE REQUIRED NFPA FIRE RATED TENANT/CORRIDOR
 SEPARATION WALLS.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED,
 ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON
 THE PLAN SHEET.
  
  
  
 3) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  