2023-05-25 16:01:48 | SPOKE WITH APPLICANT 6/2/23 10:30AM, HE STATED THAT |
| THEY HAVE ANY EXISTING FLOORING PERMIT 22111032 THAT |
| WAS APPROVED AND IS RELATED TO THIS PERMIT AND |
| SHOULD HAVE BEEN INDICATED ON THIS PERMIT. |
| |
| FLOORING COMMENT ADDRESSED. |
| |
| COMMNETS 2 & 3 WILL BE CHANGED TO PROVISO, 4 & 5 NO |
| LONGER APPLY: APPLICANT ACKNOWLEDGED. |
| |
| FIRE PROVISO: |
| |
| 1) THERE ARE INDICATIONS OF BATHROOM WORK THAT MAY |
| INVOLVE REQUIRED NFPA FIRE RATED TENANT/CORRIDOR |
| SEPARATION WALLS. |
| |
| ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON |
| THE PLAN SHEET. |
| |
| |
| |
| 2 ) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| EQUIPMENT. |
| |
| DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| DEVICES/EQUIPMENT. |
| |
| THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| DEMO AND CONSTRUCTION. |
| |
| PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| ******************************************************* |
| ******************************************************* |
| ****************************** |
| |
| |
| THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS NO INDICATION OF A FLOORING TYPE, |
| MANUFACTURER'S SPECIFICATION SHEET NOR A PRODUCT NAME. |
| |
| FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL |
| ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| TYPE THE PRODUCT ANMCE AND SPEC SHEETS INDICATING THE |
| FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF BATHROOM WORK THAT MAY |
| INVOLVE REQUIRED NFPA FIRE RATED TENANT/CORRIDOR |
| SEPARATION WALLS. |
| |
| ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON |
| THE PLAN SHEET. |
| |
| |
| |
| 3) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| EQUIPMENT. |
| |
| DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| DEVICES/EQUIPMENT. |
| |
| THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| DEMO AND CONSTRUCTION. |
| |
| PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |