Plan Review Notes
Plan Review Notes For Permit 23051214
Permit Number 23051214
Review Stop Z
Sequence Number 1
Notes
Date Text
2023-07-11 16:01:08** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR IN ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ALL NEW POLE FIXTURES MUST MATCH THE APPROVED SITE
 PLAN AND MUST BE SETBACK A MINIMUM OF 5 FT. FROM THE
 PROPERTY LINE.
  
 2.) PLEASE IDENTIFY WHICH POLE FIXTURES ARE NEW AND
 WHICH ARE EXSITING IN THE SITE PLAN.
  
 3.) POLE FIXTURE SETBACK DISTANCE FROM THE EDGE OF THE
 POLE TO THE PROPERTY LINE SHALL BE PROVIDED IN THE
 PLANS. THE DISTANCE (FOR ALL NEW FIXTURES MUST BE
 CONSISTENT WITH THE SETBACK REQUIREMENTS OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS)).
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTATC LINDA LOUIE @ 561.822.1458 OR [email protected]
 IF THERE ARE QUESTIONS.
  
 * Z = CPD (PALM BEACH RIVERSTONE - RESIDENTIAL POD)
  
 * MASTER PERMIT #20120803
  