Plan Review Notes For Permit 23051034 |
Permit Number |
23051034 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-06-22 19:07:33 | PLAN REVIEWER: ED ROSEBERRY PX2909 | | EMAIL: [email protected] | | PH: 772-359-3502 | | ***PRIMARY CONTACT IS EMAIL*** | | | | 1. PLEASE SUBMIT OCCUPANCY CLASSIFICATION AND SUBMIT | | HARDWARE DETAIL COMPLYING WITH FBC 10.1.9 | | 2. PLEASE SUBMIT COMPLETE FBC/NOA FOR ALL REPLACEMENT | | FENESTRATION, WITH SPECIFIC MODELS, SIZES, AND DESIGN | | PRESSURE TABLES HIGHLIGHTED. DP MUST BE HIGHLIGHTED. | | FBC 107.2 | | 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO | | THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR | | FBC B 1405.4. |
|