2023-05-24 11:42:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS AN INDICATION OF A MODULE UNIT WITH A |
| PROPOSED USE AS AN EDUCATIONAL OCCUPANCY, HOWEVER, |
| THERE IS NO INDICATION OF A FIRE SPRINKLER PROTECTION, |
| |
| PER NFPA 101, CH 14, NEW EDUCATIONAL OCCUPANCIES. |
| |
| 14.3.5 EXTINGUISHMENT REQUIREMENTS. |
| |
| 14.3.5.1 EDUCATIONAL OCCUPANCY BUILDINGS SHALL BE |
| PROTECTED THROUGHOUT |
| BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| IN ACCORDANCE |
| WITH SECTION 9.7 EXCEPT AS OTHERWISE PERMITTED BY |
| 14.3.5.2. |
| 14.3.5.2 THE REQUIREMENT OF 14.3.5.1 SHALL NOT APPLY TO |
| ANY OF THE |
| FOLLOWING: |
| (1) NON-RELOCATABLE BUILDINGS HAVING AN AREA NOT |
| EXCEEDING 1000 FT2 |
| (93 M2 |
| ) |
| (2) NON-RELOCATABLE BUILDINGS CONTAINING A SINGLE |
| CLASSROOM |
| (3) RELOCATABLE BUILDINGS COMPLYING WITH ALL OF THE |
| FOLLOWING: |
| (A) BUILDING AREA DOES NOT EXCEED 1000 FT2 |
| (93 M2 |
| ) |
| (B) BUILDING CONTAINS A SINGLE CLASSROOM |
| (C) BUILDING IS LOCATED NOT LESS THAN 30 FT (9.1 M) |
| FROM ANOTHER |
| BUILDING |
| 14.3.5.3 EVERY PORTION OF EDUCATIONAL BUILDINGS BELOW |
| THE LEVEL OF EXIT |
| DISCHARGE SHALL BE PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| 9.7. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGMENT TO PROVIDE A SEPARATE PERMIT & SHOP |
| DRAWINGS. |
| |
| |
| |
| 2) THERE IS AN INDICATION OF A MODULE UNIT WITH A |
| PROPOSED USE AS AN EDUCATIONAL OCCUPANCY, HOWEVER, |
| THERE IS NO INDICATION OF A FIRE ALARM PROTECTION. |
| |
| PER NFPA 101, CH 14, NEW EDUCATIONAL OCCUPANCIES. |
| |
| 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 14.3.4.1 GENERAL. |
| 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED |
| WITH A FIRE ALARM |
| SYSTEM IN ACCORDANCE WITH SECTION 9.6. |
| 14.3.4.1.2 THE REQUIREMENT OF 14.3.4.1.1 SHALL NOT |
| APPLY TO BUILDINGS |
| MEETING ALL OF THE FOLLOWING CRITERIA: |
| (1) BUILDINGS HAVING AN AREA NOT EXCEEDING 1000 FT2 |
| (93 M2 |
| ) |
| (2) BUILDINGS CONTAINING A SINGLE CLASSROOM |
| (3) BUILDINGS LOCATED NOT LESS THAN 30 FT (9.1 M) FROM |
| ANOTHER |
| BUILDING |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGMENT TO PROVIDE A SEPARATE PERMIT & SHOP |
| DRAWINGS. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |