2023-06-12 09:58:072ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23051029
 6/12/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE 1ST REVIEW COMMENTS CONCERNING
 WATER SERVICE AND SANITARY FACILITIES THE ARCHITECT IS
 STATING THE MODULE UNITS ARE "DRY" UNITS THAT THE
 STUDENTS WILL USE THE FACILITIES IN THE SOUTH BUILDING.
 IN ORDER TO VERIFY THE REQUIRED NUMBER OF PLUMBING
 FIXTURES WILL BE PROVIDED PLEASE PROVIDE FIXTURE
 CALCULATIONS FOR THE COMBINED STUDENT AND STAFF
 OCCUPANT LOAD OF THE TEMPORARY MODULE UNITS AND THE
 SOUTH BUILDING- SEC. 108.2 WPB, SEC. 403.3 & TABLE
 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED NUMBER OF FIXTURES AND THE EXISTING NUMBER OF
 FIXTURES IN THE SOUTH BUILDING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  