Plan Review Notes
Plan Review Notes For Permit 23051029
Permit Number 23051029
Review Stop P
Sequence Number 1
Notes
Date Text
2023-05-24 11:37:461ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051029
 5/24/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS-002 SITE PLAN: PROVIDE POTABLE WATER SERVICE LINE
 DETAILS FOR THE TEMPORARY MODULAR CLASSROOM UNIT- SECS.
 301.4, 602.1, 602.2, & 605.3 FBC P. SHOW THE TYPE AND
 SIZE OF SERVICE LINE, SERVICE LINE RUN, POINT OF
 CONNECTION TO THE CITY MAIN, AND THE LOCATIONS OF THE
 WATER METER AND BACKFLOW PREVENTER. INDICATE THE TYPE
 AND SIZE OF BACKFLOW PREVENTER TO BE INSTALLED- SEC.
 608.3 FBC P AND SEC. E WPB UTILITIES CROSS CONNECTION
 MANUAL. PLEASE NOTE A SEPARATE PLUMBING OR CIVIL PLAN
 MAY SUBMITTED AS ALTERNATES TO REVISING THE SITE PLAN-
 SEC. 107.2.1 WPB.
 A) CONCERNING THE BACKFLOW PREVENTER PLEASE NOTE A
 PERMIT APPLICATION SHALL BE SUBMITTED FOR THE
 INSTALLATION PRIOR TO APPROVAL OF THE PLUMBING PLAN
 REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE
 THE REVIEW STATUS TO PASS.
  
 2) AS-002 SITE PLAN: PROVIDE A SANITARY DRAINAGE PLAN
 FOR THE MODULAR UNIT- SEC 701.2 & 701.3 FBC P. PROVIDE
 EITHER A DIRECT PIPE CONNECTION TO THE CITY SEWER LINE
 OR AN ONSITE SYSTEM SUCH AS A HOLDING TANK WITH
 PUMP-OUT CAPABILITY.
 A) SEWER CONNECTION- SHOW THE TYPE AND SIZE OF BUILDING
 DRAIN PIPE, THE DRAIN PIPE RUN, POINT OF CONNECTION TO
 THE SEWER LINE, AND CLEANOUT LOCATIONS.
 B) PUMP TANK- SHOW THE LOCATION OF THE TANK ON THE
 PLAN, PROVIDE A PIPING DIAGRAM, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  