Plan Review Notes
Plan Review Notes For Permit 23051029
Permit Number 23051029
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-24 11:42:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A MODULE UNIT WITH A
 PROPOSED USE AS AN EDUCATIONAL OCCUPANCY, HOWEVER,
 THERE IS NO INDICATION OF A FIRE SPRINKLER PROTECTION,
  
 PER NFPA 101, CH 14, NEW EDUCATIONAL OCCUPANCIES.
  
 14.3.5 EXTINGUISHMENT REQUIREMENTS.
  
 14.3.5.1 EDUCATIONAL OCCUPANCY BUILDINGS SHALL BE
 PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 IN ACCORDANCE
 WITH SECTION 9.7 EXCEPT AS OTHERWISE PERMITTED BY
 14.3.5.2.
 14.3.5.2 THE REQUIREMENT OF 14.3.5.1 SHALL NOT APPLY TO
 ANY OF THE
 FOLLOWING:
 (1) NON-RELOCATABLE BUILDINGS HAVING AN AREA NOT
 EXCEEDING 1000 FT2
 (93 M2
 )
 (2) NON-RELOCATABLE BUILDINGS CONTAINING A SINGLE
 CLASSROOM
 (3) RELOCATABLE BUILDINGS COMPLYING WITH ALL OF THE
 FOLLOWING:
 (A) BUILDING AREA DOES NOT EXCEED 1000 FT2
 (93 M2
 )
 (B) BUILDING CONTAINS A SINGLE CLASSROOM
 (C) BUILDING IS LOCATED NOT LESS THAN 30 FT (9.1 M)
 FROM ANOTHER
 BUILDING
 14.3.5.3 EVERY PORTION OF EDUCATIONAL BUILDINGS BELOW
 THE LEVEL OF EXIT
 DISCHARGE SHALL BE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT TO PROVIDE A SEPARATE PERMIT & SHOP
 DRAWINGS.
  
  
  
 2) THERE IS AN INDICATION OF A MODULE UNIT WITH A
 PROPOSED USE AS AN EDUCATIONAL OCCUPANCY, HOWEVER,
 THERE IS NO INDICATION OF A FIRE ALARM PROTECTION.
  
 PER NFPA 101, CH 14, NEW EDUCATIONAL OCCUPANCIES.
  
 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 14.3.4.1 GENERAL.
 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE WITH SECTION 9.6.
 14.3.4.1.2 THE REQUIREMENT OF 14.3.4.1.1 SHALL NOT
 APPLY TO BUILDINGS
 MEETING ALL OF THE FOLLOWING CRITERIA:
 (1) BUILDINGS HAVING AN AREA NOT EXCEEDING 1000 FT2
 (93 M2
 )
 (2) BUILDINGS CONTAINING A SINGLE CLASSROOM
 (3) BUILDINGS LOCATED NOT LESS THAN 30 FT (9.1 M) FROM
 ANOTHER
 BUILDING
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT TO PROVIDE A SEPARATE PERMIT & SHOP
 DRAWINGS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  