Plan Review Notes
Plan Review Notes For Permit 23050980
Permit Number 23050980
Review Stop E
Sequence Number 1
Notes
Date Text
2023-05-31 07:52:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INFORMATIONAL NOTE. NO CT METER HAS BEEN INSTALLED
 ON SERVICE TO FIRE PUMP CONTROLLER IN THE FIELD.
  
 2. ON SHEET E5.5 NO WIRE SIZES ARE SHOWN ON "GENERATOR
 RISER DIAGRAM" PLEASE SHOW ALL WIRE SIZES.
  
 3. SHOW LAYOUT AND PLACEMENT OF NEW 400AMP ATS IN
 ELECTRICAL ROOM SHOWING ALL PROPER WORKING CLEARANCES
 PER NEC 110.26. ATS HAS BEEN INSTALLED PRIOR TO AN
 APPROVED REVISION FROM THE AHJ. FBC 107.2.1 FBC 107.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved