2023-05-31 07:52:56 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. INFORMATIONAL NOTE. NO CT METER HAS BEEN INSTALLED |
| ON SERVICE TO FIRE PUMP CONTROLLER IN THE FIELD. |
| |
| 2. ON SHEET E5.5 NO WIRE SIZES ARE SHOWN ON "GENERATOR |
| RISER DIAGRAM" PLEASE SHOW ALL WIRE SIZES. |
| |
| 3. SHOW LAYOUT AND PLACEMENT OF NEW 400AMP ATS IN |
| ELECTRICAL ROOM SHOWING ALL PROPER WORKING CLEARANCES |
| PER NEC 110.26. ATS HAS BEEN INSTALLED PRIOR TO AN |
| APPROVED REVISION FROM THE AHJ. FBC 107.2.1 FBC 107.4 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |