2023-07-18 17:33:41FAILED
  
 1) THE INSTALLATION OF THE NEW ALUMINUM METAL PANEL AT
 THE ENTRY DOOR TRANSOM REDUCES THE AMOUNT OF GLAZING
 ALONG THE EASTERN STOREFRONT. PROVIDE VERIFICATION THAT
 THE MINIMUM PERCENTAGE OF GLAZING (50 PERCENT OF THE
 FRONTAGE) IS STILL BEING PROVIDED.
  
 2) SHEET S-002 SHOWS A STAIR DETAIL. WHERE IS THIS TO
 BE LOCATED AS THE FLOOR PLANS DO NOT SHOW A STAIR?
 PLEASE NOTE, NO MEZZANINE IS PERMITTED IN THIS UNIT.
  