2023-06-22 10:07:00PLAN DENIED
 1) PROVIDE OUTDOOR AIR CALCULATIONS TO MEET
 TABLE 403.1.1 FBC (M) 2020
 2) NOT SHOWING DUCTWORK ON UNITS 2, 3, OR 4
 PLEASE EXPLAIN WHY. SECTION 107 FBC.
 3) PLEASE LABEL ALL ROOMS FOR THIS REVIEW.
 107 FBC
 4) REFER TO SECTION C403.2.1 CALCULATIONS
 OF HEATING AND COOLING LOADS. FBC (ENERGY)