Plan Review Notes
Plan Review Notes For Permit 23050963
Permit Number 23050963
Review Stop B
Sequence Number 1
Notes
Date Text
2023-05-22 14:21:35ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PRODUCT APPROVAL FL5259-R38 FOR THE UNDERLAYMENT -
 SYSTEM NUMBER UDL-2 (-90.0) IS CIRCLED WHICH DOES NOT
 MEET THE REQUIRED PRESSURE PER THE FRSA/TRI FLORIDA
 HIGH WIND CONCRETE AND CLAY ROOF TILE INSTALLATION
 MANUAL TABLE 1A
  
 2) PLEASE SHOW THE MEAN ROOF HEIGHT - FBC 107.2.1.1