2023-07-21 16:04:47 | PETER E VALENTI |
| BUILDING PLANS EXAMINER II/INSPECTOR |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| 3RD BUILDING REVIEW DENIED: |
| |
| NOTE: BELOW LISTED IS THE BREAKDOWN OF THE REASON FOR |
| FAILURE. |
| WHAT IS REQUIRED IS TO PROVIDE A FLOORING UNDERLAYMENT |
| THAT WORKS FOR THE WOOD FLOOR AND WAS NOT TESTED WITH |
| AN INSULATED GYPSUM BOARD SUSPENDED CEILING. THE TEST |
| REPORTS STILL HAVE TO COVER SOUND AND FLAME SPREAD |
| UNDER ASTM E 492, ASTM E 90 & ASTM E 84. |
| |
| |
| 2.) THE (2) TEST REPORTS THAT WERE SUBMITTED ARE NOT |
| APPLICABLE TO THIS PROJECT. THE ASTM E 492 TEST REPORT |
| (PROFLEX MSC 90) IS FOR PORCELAIN TILE FLOORING AND FOR |
| SITUATIONS WHERE THERE IS A DROPPED CEILING. THE OTHER |
| TEST REPORT IS FOR ASTM E 84 (PROFLEX SUPER-SIM 90) |
| WHICH IS FOR FLAME SPREAD OF PORCELAIN TILE AND RED OAK |
| FLOORING. |
| |
| THERE WERE NO TEST REPORTS FOR THE UNDERLAYMENT/MAPEI |
| ULTRABOND 980 SUBMITTED. PLEASE NOTE THAT TEST REPORTS |
| ARE REQUIRED - MANUFACTURER SPEC SHEETS ARE NOT |
| ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC |
| SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER |
| SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |