2023-05-24 08:54:09 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23050901 |
| 5/23/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET LS-101: PROVIDE THE OCCUPANT LOAD OF THE |
| BUILDING AND PLUMBING FIXTURE CALCULATIONS IN |
| ACCORDANCE WITH TABLE 403.1 FBC P. INDICATE THE |
| REQUIRED AND PROVIDED NUMBER OF FIXTURES. |
| A) THE PLANS SHOW NUMEROUS SINGLE DRINKING FOUNTAINS. |
| PLEASE NOTE WHERE DRINKING FOUNTAINS ARE REQUIRED NOT |
| FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE |
| DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS |
| FOR STANDING PERSONS. PLEASE REFER TO EXCEPTION 1 WHICH |
| ALLOWS A SINGLE FOUNTAIN WITH TWO SEPARATE HI AND LO |
| SPOUTS TO MEET COMPLIANCE |
| |
| 2) P-001, P-202, P-204, & P-302: REFER TO 468.3.5.6 FBC |
| B AND PROVIDE HOSE BIBS IN EACH MALE AND FEMALE GROUP |
| TOILET ROOM. |
| A) VERIFY THE FLOORS ARE SLOPED TO THE FLOOR DRAINS IN |
| THE GROUP TOILET ROOMS. |
| |
| 3) P-001, P-202, P-204, & P-302: REFER TO SEC. |
| 468.3.5.1.2 FBC B AND VERIFY POINT OF USE MIXING VALVES |
| SHALL BE INSTALLED AT ALL HANDWASH SINKS AND LAVATORIES |
| TO LIMIT THE HOT WATER DELIVERY TEMPERATURE TO 110 |
| DEGREES F. PLEASE ADD THE LISTING NUMBERS OF THE VALVES |
| SPECIFIED IN THE SCHEDULE. |
| |
| 4) P-001, P-202, P-204, & P-302: PROVIDE AN ASSE 1071 |
| MIXING VALVE TO THE WATER SUPPLY LINES TO THE EMERGENCY |
| SHOWER AND EYE WASH STATIONS IN ACCORDANCE WITH TO ISEA |
| Z358.1 SPECIFICATIONS- SEC. 411.1 FBC P. |
| |
| 5) P-201, P-203, P-302: BASED ON SEC. 803.1 FBC P THE |
| DRAINAGE FROM THE LAB SINKS AND THE EMERGENCY SHOWERS |
| AND EYEWASH STATIONS SHALL PASS THROUGH A DILUTION OR |
| NEUTRALIZING DEVICE BEFORE DISCHARGING INTO THE |
| SANITARY SYSTEM. |
| |
| 6) P-402: THE UTILITY CONTROL DETAIL FOR THE SCIENCE |
| CLASSROOMS APPEARS TO INDICATE NATURAL OR LP GAS |
| SERVICE IS BEING PROVIDED TO THE ROOMS. PLEASE CLARIFY |
| AND IF APPLICABLE PROVIDE GAS PLANS INCLUDING A RISER |
| DIAGRAM, EQUIPMENT SPECIFICATIONS, COMBUSTION AIR |
| CALCULATIONS AND APPLIANCE VENTING DIAGRAMS AND |
| SPECIFICATIONS- SEC. 107.2.1 & 107.3.5.1.5 WPB. |
| |
| 7) A-212: PROVIDE ENLARGED DIMENSIONED DRAWINGS OF THE |
| WHEELCHAIR ACCESSIBLE TOILET COMPARTMENTS SHOWING THE |
| CLEAR FLOOR SPACE DIAGRAMS FOR THE FIXTURES- SECS. |
| 604.3 & 604.8 FBC ACC. |
| A) PROVIDE THE DIMENSIONS AMBULATORY COMPARTMENTS AND |
| ACCESSORY INSTALLATION DETAILS- SEC. 604.8.2- 604.8.2.3 |
| FBC ACC. |
| B) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS |
| FOR THE REQUIRED ACCESSIBLE URINALS- SECS. 213.3.3 & |
| 605.3 FBC ACC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |