2023-05-25 12:46:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 402 & A 600 - THERE IS AN INDICATION OF DOOR
 201 AS BEING SMOKE RATED YET OTHER DOORS IN THE
 STAIRWELLS INCLUDING DOOR 220 AS BEING 45 MINUTE.
  
 PER NFPA 101, CH 14 EDUCATIONAL OCCUPANCIES.
  
 7..2.2.5 ENCLOSURE AND PROTECTION OF STAIRS
  
 7.2.2.5.1 ENCLOSURES
  
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT SHALL
 BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2
  
 7.1.3.2 EXITS.
  
 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE
 SEPARATED FROM OTHER
 PARTS OF THE BUILDING, THE SEPARATING CONSTRUCTION
 SHALL MEET THE REQUIRE MENTS OF SECTION 8.2 AND THE
 FOLLOWING:
 (1)* THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE
 RESISTANCE RATING
 WHERE THE EXIT CONNECTS THREE OR FEWER STORIES
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 1A) SHEET A 402 & A 600 - THERE ARE INDICATIONS OF NEW
 WALLS WITHIN THE STAIRWAYS SUPPORTING DOORS 201 AND 220
 THAT DO NOT APPEAR TO BE 1 - HR RATED AS REQUIRED
 PER THE CH 14 FIRE CODES ABOVE.
  
 PLEASE REVIEW AND PROVIDE FOR LISTED 1 HR FIRE RATED
 WALLS.
  
  
  
 2) LIFE SAFETY SHEETS - THERE IS AN INDICATION OF
 CLASSROOM DOORS OPENING OUT INTO THE CORRIDOR.
  
 PER NFPA 101, CH 14
  
 14.2.3.2 MINIMUM CORRIDOR WIDTH.
 14.2.3.2.1 EXIT ACCESS CORRIDORS SHALL HAVE NOT LESS
 THAN 6 FT (1830 MM)
 OF CLEAR WIDTH EXCEPT AS OTHERWISE PERMITTED IN
 14.2.3.2.2.
  
 NARRATIVE EXPLANATION: THE TERM CLEAR WIDTH MEANS A 6
 FT (1830 MM) WIDE CLEAR
 SPACE WITH NO OBSTRUCTIONS OTHER THAN THOSE PERMITTED
 BY 7.3.2.2
 AND DOORS AS PERMITTED BY 7.2.1.4.3. SUBSECTION 7.3.2
 DETAILS THE
 REQUIRED METHOD FOR MEASURING THE WIDTH OF A COMPONENT
 OF THE
 MEANS OF EGRESS. PARAGRAPH 7.3.2.2 PERMITS PROJECTIONS
 OF NOT
 MORE THAN 4 1???2 IN. (114 MM) ON EACH SIDE OF THE
 CORRIDOR. THE PROJECTIONS
 ARE PERMITTED TO BE LOCATED AT OR BELOW A HANDRAIL
 HEIGHT
 OF 38 IN. (965 MM), AND THE MAXIMUM 4 1???2 IN. (114
 MM)
 ENCROACHMENT IS TO BE IGNORED WHEN DETERMINING WIDTH
 FOR USE
 IN EGRESS CAPACITY CALCULATIONS
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
  
 A.7.2.1.4.3 THE REQUIREMENTS OF 7.2.1.4.3 ARE NOT
 INTENDED TO APPLY TO
 THE SWING OF CROSS-CORRIDOR DOORS, SUCH AS SMOKE
 BARRIER DOORS AND
 HORIZONTAL EXITS. NEITHER ARE THE REQUIREMENTS INTENDED
 TO APPLY TO DOORS
 FROM ROOMS THAT ARE TYPICALLY UNOCCUPIED, SUCH AS
 JANITOR???S CLOSETS,
 ELECTRICAL CLOSETS, OR TELECOMMUNICATIONS CLOSETS
  
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVI SIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS TRAVEL
  
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  