2023-05-24 09:48:22 | ELECTRIC REVIEW FAILED |
| |
| PLEASE PROVIDE A NARRATIVE RESPONSE IN ADDITION TO ANY |
| PLAN CHANGES TO EACH OF THE FOLLOWING COMMENTS: |
| |
| 1) ELECTRICAL WORK SCOPE IS NOT CLEAR. PLEASE PROVIDE A |
| NARRATIVE AS WELL AS PLANS INDICATING PROPOSED AND |
| EXISTING WORK, INCLUDING ALL TYPE AND LOCATIONS WHERE |
| WORK IS TO BE PERFORMED. I.E. NEW SWITCHGEAR AND PANEL |
| BOARDS, DUCT BANKS. FBC 107.2 NEC 215.5 |
| |
| 2) SITE PLAN INDICATES NO WORK CAMPUS MAIN ELECTRIC |
| ROOM. HOWEVER, IT APPEARS A NEW MAIN SWITCH BOARD IS TO |
| BE INSTALLED IN THIS BUILDING. PLEASE CORRECT OR |
| PROVIDE ADDITIONAL CLARITY ON EQUIPMENT LOCATIONS. IN |
| ADDITION, IT APPEARS THIS CAMPUS MAIN ELECTRIC ROOM IS |
| LOCATED IN A MAINTENANCE BUILDING, HOWEVER THERE IS NO |
| LOCATION GIVEN FOR THIS BUILDING ON SITE PLAN. LOCATION |
| DESIGNATIONS IN MANY AREAS ARE NOT CLEAR. FBC 107.2 |
| |
| 3) PLEASE USE THE PROPER IDENTIFYING NAMES ON ALL PLANS |
| FOR ELECTRICAL EQUIPMENT. I.E. NOTE 4 ON SITE PLAN, |
| MAIN ELECTRIC PANEL SHOULD BE CORRECTLY IDENTIFIED WITH |
| PANEL DESIGNATION. FBC 107.2 |
| |
| 4) PROVIDE A MAIN ELECTRICAL ROOM FLOOR PLAN AS |
| REFERENCED BY NOTE 1 ON SHEET E-401. FBC 107.2 |
| |
| 5) PLEASE INDICATE PURPOSE OF REFERRING TO SWBD AS MAIN |
| 1 OF 1. PLEASE PROVIDE CLARITY OF THE PURPOSE OF THIS |
| DESIGNATION. FBC 107.2 |
| |
| 6) PLEASE PROVIDE ADDITIONAL CLARITY OF RISER DIAGRAM |
| FOR MULTIPLE FEEDS TO MODULAR SWITCHBOARD. NEC 215.5 |
| |
| 7) PLEASE ADD A NOTE STATING SEPARATE PERMITS ARE |
| REQUIRED FOR ALL LOW VOLTAGE SYSTEMS SUCH AS BUT NOT |
| LIMITED TO, FIRE ALARM, VOICE, DATA, SECURITY, ACCESS |
| CONTROL ETC. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |
| |