Plan Review Notes For Permit 23050901 |
Permit Number |
23050901 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-05-23 14:36:29 | REMODEL AND ENTRY ADDITIONS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS | | AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | OF RECORD OR BE LISTED ON THE DRAWINGS BY THE PERMIT | | NUMBER - FBC 107.3.4 | | | | EXTERIOR WINDOW, DOOR AND ROOFING SYSTEM PRODUCT | | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS | | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC | | WPB107.3.4.1 | | | | 2) THE LIFE SAFETY DRAWINGS SHOW FIRE RATED WALLS AND | | POSSIBLE SMOKE RATED WALLS - PLEASE PROVIDE A LEGEND TO | | CLARIFY THE MARKINGS ON THE LIFE SAFETY DRAWINGS - FBC | | 107.2.1 | | | | 3) DOOR NUMBER 201 SHOULD BE FIRE RATED - IT IS SHOWN | | AS NOT FIRE RATED ON THE DOOR SCHEDULE FBC 716 | | | | 4) PLEASE SHOW THE RESTROOM CEILINGS TO BE IMPERVIOUS - | | FBC 468.3.5.10 CEILINGS. | | CEILINGS IN GROUP TOILET ROOMS, KITCHENS, SCULLERIES, | | CAN WASH AREAS, SHOWERS AND LOCKER ROOMS SHALL BE | | IMPERVIOUS. | | |
|