Plan Review Notes
Plan Review Notes For Permit 23050838
Permit Number 23050838
Review Stop P
Sequence Number 2
Notes
Date Text
2023-07-06 08:21:552ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23050838
 7/623
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE KITCHEN SINK AND DISHWASHER LIKE FOR LIKE
 REPLACEMENTS ARE APPROVED HOWEVER A NEW 000 FLOOR PLAN
 HAS BEEN SUBMITTED SHOWING AN AS-BUILT BATHROOM WHICH
 IS NOT PART OF THE ORIGINAL SCOPE OF WORK FOR THE
 KITCHEN REMODEL.
 THE CONTRACTOR SHALL PROVIDE FURTHER INFORMATION TO
 CLARIFY THE SCOPE OF WORK FOR THE BATHROOM AND A
 ITEMIZED BREAKDOWN OF COSTS ASSOCIATED WITH THE WORK-
 SEC. 107.2.1 WPB.
  
 A) PLEASE INDICATE IF THIS IS A NEW BATHROOM, OR
 BATHROOM WITH REPLACED OR RELOCATED FIXTURES. PROVIDE
 NOTES TO CLARIFY.
 B) PROVIDE PLUMBING RISER DRAWINGS FOR NEW OR EXTENDED
 PIPING INSTALLATIONS- SEC. 107.3.5.1.3 WPB.
 C) PROVIDE FIRESTOPPING DETAILS FOR NEW DRAIN PIPES
 PENETRATING FIRE-RATED WALLS OR FLOOR SLABS- SEC. 315.1
 FBC P.
  
 2) FAIR HOUSING COMPLIANCE- THE CONDOMINIUMS AT ONE
 CITY PLAZA ARE SUBJECT TO COMPLIANCE WITH FAIR HOUSING
 ACCESSIBILITY GUIDELINES WHICH CAME INTO EFFECT FOR
 MULTIFAMILY HOUSING BUILT FOR FIRST OCCUPANCY AFTER
 MARCH 13, 1991. THE SUBMITTED AS-BUILT FLOOR PLAN PLAN
 SHOWING A NEW SHOWER MUST BE MODIFIED IN ACCORDANCE
 WITH COMMENTS #2 & #3 BELOW. PLEASE NOTE: AS AN
 ALTERNATIVE TO MEETING THE GUIDELINES FOR THE BATHROOM
 PLAN, THE OWNER AND DESIGNER OF RECORD FOR THE PROPOSED
 PROJECT MAY PROVIDE A SIGNED AND NOTARIZED AFFIDAVIT
 WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE PROPOSED
 DESIGN DOES NOT MEET THE REQUIREMENTS OF THE FAIR
 HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO REQUIRE
 THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF REQUESTED BY THE BUYER.
 IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO
 [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
 2) REFER TO PAGES 7.56- 7.59 OF THE FHDA MANUAL AND
 PROVIDE A DRAWING FOR THE BATHROOM THAT SHOWS THE
 DIMENSIONS OF THE SHOWER AND THE REQUIRED 30X48-INCH
 CLEAR FLOOR SPACE DIAGRAM POSITIONED PARALLEL TO THE
 SHOWER AND FLUSH WITH THE CONTROL WALL. PLEASE NOTE NO
 OTHER FIXTURES SHALL OBSTRUCT THE CLEAR FLOOR SPACE
 REQUIRED FOR THE SHOWER WITH THE EXCEPTION OF A
 LAVATORY WHICH MAY OVERLAP BY 6-INCHES. THE LAVATORY
 SHALL BE A WALL HUNG WITH KNEE AND TOE CLEARANCES OR
 HAVE A REMOVABLE CABINET.
  
 3) PROVIDE AN ELEVATION DETAIL FOR THE SHOWER THAT
 SHOWS THE LOCATIONS OF REQUIRED GRAB BAR REINFORCEMENTS
 IN ACCORDANCE WITH PAGE 6.13.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  