Date |
Text |
2023-05-22 17:08:01 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23050763 |
| 5/22/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SEPARATE PERMITS ARE REQUIRED FOR THE POTABLE WATER |
| BACKFLOW PREVENTER AND THE GREASE INTERCEPTOR. AT A |
| MINIMUM, THE PERMIT APPLICATIONS FOR EACH SHALL BE |
| SUBMITTED PRIOR TO MAIN PLUMBING PLAN APPROVAL. IF |
| CONTRACTORS ARE NOT CURRENTLY SELECTED FOR EACH |
| INSTALLATION, PERMIT APPLICATIONS CAN BE SUBMITTED TBD |
| (TO BE DETERMINED). EACH COMPLETED APPLICATION SHALL BE |
| EMAILED TO [email protected] . YOU WILL THEN |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND |
| THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA |
| EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| 2) SHEETS A301, P101, & P700: THE 8-INCH GUTTER IS |
| UNDERSIZED FOR 552 GPM ROOF DRAINAGE FLOW ACCORDING TO |
| TABLE 1106.6 FBC P. |
| |
| A) REFER TO TABLE 1106.3 AND PROVIDE THE DOWNSPOUT |
| SIZES. |
| |
| 3) P100: KEYNOTES 2, 3, 5, 8, & 10 REFER TO CIVIL |
| DRAWINGS WHICH WERE NOT UPLOADED FOR REVIEW. PLEASE |
| PROVIDE THE DRAWINGS- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |