Plan Review Notes
Plan Review Notes For Permit 23050763
Permit Number 23050763
Review Stop B
Sequence Number 1
Notes
Date Text
2023-06-08 11:57:16RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE BUILDING
 DISTANCE FROM THE PROPERTY LINES - FBC WPB 107.2.5 SITE
 PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
  
 2) EXTERIOR DOORS CANNOT ENCROACH INTO THE PUBLIC WAY -
 FBC 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET
 IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 3) PLEASE SHOW THE RAMP SLOPE - FBC A 405.2
  
 4) PLEASE SHOW THE FIRE WALL EXTENSIONS (IF USING ONE
 OF THE EXCEPTIONS SHOW THE DIMENSIONS AND FIRE RATED
 OPENINGS) - FBC 706.5 HORIZONTAL CONTINUITY.
 FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO
 EXTERIOR WALL AND SHALL EXTEND NOT LESS THAN 18 INCHES
 (457 MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS.
  
 5) THE LIFE SAFETY PLAN SHOWS NO FIRE WALLS - DRAWING
 A.101 SHOWS SOME FIRE WALLS - PLEASE CLARIFY AND SHOW
 THE HOURLY FIRE RATINGS - FBC 701
  
 6) DRAWING A.101 - WASTE ROOM - FIRE WALLS ARE SHOWN
 WITHOUT AN HOURLY RATING - IS THE DOOR TO BE FIRE RATED
 ? FBC 701
  
 7) PLEASE PROVIDE A SIGNED AND SEALED ANALYSIS REPORT
 FROM A DESIGN PROFESSIONAL ON THE EXISTING BUILDING
 MEETING THE HIGHER WIND LOADS OF A RISK CATEGORY III AS
 STATED ON THE DRAWINGS - FBC EXISTING BUILDING 1007.2
 SNOW AND WIND LOADS. BUILDINGS AND STRUCTURES SUBJECT
 TO A CHANGE OF OCCUPANCY WHERE SUCH CHANGE IN THE
 NATURE OF OCCUPANCY RESULTS IN HIGHER WIND OR SNOW RISK
 CATEGORIES BASED ON THE FLORIDA BUILDING CODE, BUILDING
 TABLE 1604.5, (HIGH-VELOCITY HURRICANE ZONES SHALL
 COMPLY WITH SECTION 1620) SHALL BE ANALYZED AND SHALL
 COMPLY WITH THE APPLICABLE WIND OR SNOW LOAD PROVISIONS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  