2023-06-08 11:57:16 | RENOVATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE PROVIDE A SITE PLAN SHOWING THE BUILDING |
| DISTANCE FROM THE PROPERTY LINES - FBC WPB 107.2.5 SITE |
| PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE |
| APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE |
| PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT |
| SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |
| |
| 2) EXTERIOR DOORS CANNOT ENCROACH INTO THE PUBLIC WAY - |
| FBC 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET |
| IN HEIGHT. |
| ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR |
| PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| |
| 3) PLEASE SHOW THE RAMP SLOPE - FBC A 405.2 |
| |
| 4) PLEASE SHOW THE FIRE WALL EXTENSIONS (IF USING ONE |
| OF THE EXCEPTIONS SHOW THE DIMENSIONS AND FIRE RATED |
| OPENINGS) - FBC 706.5 HORIZONTAL CONTINUITY. |
| FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO |
| EXTERIOR WALL AND SHALL EXTEND NOT LESS THAN 18 INCHES |
| (457 MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS. |
| |
| 5) THE LIFE SAFETY PLAN SHOWS NO FIRE WALLS - DRAWING |
| A.101 SHOWS SOME FIRE WALLS - PLEASE CLARIFY AND SHOW |
| THE HOURLY FIRE RATINGS - FBC 701 |
| |
| 6) DRAWING A.101 - WASTE ROOM - FIRE WALLS ARE SHOWN |
| WITHOUT AN HOURLY RATING - IS THE DOOR TO BE FIRE RATED |
| ? FBC 701 |
| |
| 7) PLEASE PROVIDE A SIGNED AND SEALED ANALYSIS REPORT |
| FROM A DESIGN PROFESSIONAL ON THE EXISTING BUILDING |
| MEETING THE HIGHER WIND LOADS OF A RISK CATEGORY III AS |
| STATED ON THE DRAWINGS - FBC EXISTING BUILDING 1007.2 |
| SNOW AND WIND LOADS. BUILDINGS AND STRUCTURES SUBJECT |
| TO A CHANGE OF OCCUPANCY WHERE SUCH CHANGE IN THE |
| NATURE OF OCCUPANCY RESULTS IN HIGHER WIND OR SNOW RISK |
| CATEGORIES BASED ON THE FLORIDA BUILDING CODE, BUILDING |
| TABLE 1604.5, (HIGH-VELOCITY HURRICANE ZONES SHALL |
| COMPLY WITH SECTION 1620) SHALL BE ANALYZED AND SHALL |
| COMPLY WITH THE APPLICABLE WIND OR SNOW LOAD PROVISIONS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| |